Ambient Conditions
The AC drive should be kept in the shipping carton before installation. In order to
retain the warranty coverage, the AC drive should be stored properly when it is
not to be used for an extended period of time. Some storage suggestions are:
• Store in a clean and dry location free from direct sunlight or corrosive fumes.
• Store within an ambient temperature range of -20°C to +60°C.
• Store within a relative humidity range of 0% to 90% and non-condensing
environment.
• Store within an air pressure range of 86 kPA to 106kPA.
Chapter 2: Installation and Wiring
GS1 Series AC Drive User Manual
2–2
Ambient Conditions
Ambient Temperature
-10° to 40°C (14°F to 104°F) w/o derating
Storage Temperature
-20° to 60 ° C (-4°F to 140°F) during short-term transportation period)
Relative Humidity
0 to 90% RH (non-condensing)
Atmosphere Pressure
86 kPA to 106kPA
Vibration
9.8 m/s2(1G), less than 10Hz. 5.88 m/s2 (0.6G) 20 to 50 Hz
Installation Location
Altitude 1000m or lower above sea level, keep from corrosive gas,
liquid and dust
Enclosure Rating
Protected chassis, IP20