08. Appendix
8.5 Appendix 5 - Caution & Warning
8.6 Appendix 6 - Cable specifications
• The unit can only be repaired by a qualified installing
center, personnel, or an authorised dealer. (for
European market)
• This appliance is not intended to be used by minors
and persons with reduced physical, sensory, and/
or mental capabilities, or lack of experience and
knowledge, unless they are being supervised by a
responsible adult. Keep this equipment away from
children.
• Please make sure that the unit and power
connection have good earthing to avoid electrical
shocks.
• If the supply cord is damaged, it must be replaced
by the manufacturer, service agent, or a qualified
person in order to avoid hazards.
• Directive 2002/96/EC (WEEE): The symbol depicting
a crossed-out waste bin that is underneath the
appliance indicates that this product, at the end of
its useful life, must be handled separately from
domestic waste, must be taken to a recycling center
for electric and electronic devices, or handed back to
the dealer when purchasing an equivalent appliance.
• Directive 2002/95/EC (RoHs): This product is
compliant with directive 2002/95/EC (RoHs)
concerning restrictions on the use of harmful
substances in electric and electronic devices.
• The unit CANNOT be installed near flammable gas.
Gas leakage may cause fire.
• Make sure that there is a circuit breaker for the unit.
Lack of circuit breaker could lead to electrical shock
or fire.
• The heat pump located inside the unit is equipped
with an over-load protection system. It does not
allow the unit to start for at least 3 minutes from a
previous stoppage.
• The unit can only be repaired by qualified personnel
of an installing center or an authorized dealer. (for
North American market)
• Installation must be performed in accordance with
the NEC/CEC by authorized personnel only. (for
North American market)
• USE SUPPLY WIRES SUITABLE FOR A
TEMPERATURE OF 75ºC.
• Caution: Single wall heat exchanger is not suitable
for potable water connection.
Nameplate
max current
Phase line
Earth line
MCB
Creepage
protector
Signal line
Single Phase Unit
Three Phase Unit
No more than 10A
2x1.5mm
2
3x1.5mm
2
1.5mm
2
20A
30mA less than
0.1 sec
n×0.5mm
2
10~16A
2x2.5mm
2
3x2.5mm
2
2.5mm
2
32A
16~25A
2x4mm
2
3x4mm
2
4mm
2
40A
25~32A
2x6mm
2
3x6mm
2
6mm
2
40A
32~40A
2x10mm
2
3x10mm
2
10mm
2
63A
40~63A
2x16mm
2
3x16mm
2
16mm
2
80A
63~75A
2x25mm
2
3x25mm
2
25mm
2
100A
75~101A
2x25mm
2
3x25mm
2
25mm
2
125A
101~123A
2x35mm
2
3x35mm
2
35mm
2
160A
123~148A
2x50mm
2
3x50mm
2
50mm
2
225A
148~186A
2x70mm
2
3x70mm
2
70mm
2
250A
186~224A
2x95mm
2
3x95mm
2
95mm
2
280A
If the unit will be installed outdoors, please use the cable which can stand against UV.