11
KS 2
(24 V DC / 230 V AC)
D
ata
S
heet
KS2 S12 24v DC r / L
D
ata
s
heet
Application: natural ventilation, RWA, ferralux
®
-NRWG
Internal Intelligent Control Electronics S12
Z-Version: Programmable feedback limit position „OPEN“ or „CLOSE“
(max. 24V, 500 mA)
Options
Programmable special functions
M-COM for automatic synchronised run of multi-drive systems and
automatic sequence control with locking drives (S3 / S12)
TECHNICAL DATA
U
N
Rated voltage
24V DC (19 V ... 28 V)
I
N
Rated current
0,7 A
I
A
Cut-off current
1,0 A
P
N
Rated power
17 W
DC
Duty cycle
5 cycles (ED 30 % - ON: 3 min. / OFF: 7 min.)
Protection rating
IP 32
Ambient temperature range
-5 °C ... +60 °C
F
Z
Pulling force max.
250 N
F
A
Pushing force max.
s > 600 mm only for pulling application
F
H
Pullout force
1.800 N (fastening depended)
Chain
Stainless steel, without protruding rivet heads.
Simple connection to casement brackets.
Small bending radii allow maximum opening
angles of small windows.
Connecting cable
non-halogen, grey 3 x 0,5 mm², ~ 3 m
non-halogen, grey 5 x 0,5 mm², ~ 3 m (Z-Version)
v
Speed
s < 400
8,0 mm/s
8,0 mm/s
s > 400 – 600
12,0 mm/s
8,0 mm/s
s > 600
13,5 mm/s
8,0 mm/s
s
Stroke
50 – 1000 mm
L
Length
see order data
Sound pressure level:
≤
70 dB (A)
24V
26
41
5
13
12
13
L
s
143
R
s
26
L
13
12
13
143
41
5
L
50
0
250
150
100
200
500
400
600
300
200
s
(mm)
F
(N)
800 1000
Pull
Zug
Push
Schub
(Right)
02
(Left)
Summary of Contents for 521620