OPERATION: OPERATING FEEDBACK
MVS Series
43
710-03261-00D
Operating Feedback
10
10.1 Metering
Screens
The MVS uses metering screens to display information on the soft starter's
performance. Use the
▲
and
▼
buttons to move between metering screens.
RUNNING STOP IN 14:02
260A
M1
* 100%
L1 260 A
L2 258 A
L3 261 A
GC 260 A
6600 V 6610 V 6605 V
260 A
258 A
261 A
2515 KW
3372 HP
2970 KVA
0.92 PF
LAST START
12 S
400% FLC
T-RISE 40%
DATE/TIME
2004NOV28
11:20:36
STARTING
1040 A
11540
1080
Last start
information
Date/time
Programmable
screen
Starter status
Current
Voltage and current
Power metering
Pressing the
►
button while viewing the Date/Time screen lets the user set the
date and time on the MVS Controller. Pressing the
►
button at any other screen
opens the Programming Menu.
10.2 Starter
Status
The
starter status
screen shows real-time details of the starter's status, including
current and temperature:
Running Stop in 14:02
260A
M1
88%
Status
Auto-stop information
Parameter set
Motor temperature
Motor current
The information on the screen is arranged as follows:
•
top left: status information (Ready, Starting, Running, Stopping or Tripped).
•
top right: auto-stop information.
•
bottom left: motor current (mean average of three phases).
•
bottom centre: parameter set currently in use (primary (M1) or secondary
(M2)).
•
bottom right: motor temperature (based on the thermal model).
When the motor temperature approaches the trip level, the temperature will flash.
When the motor's thermal capacity will not permit a restart, an asterisk appears in
front of the temperature.
When a warning occurs, the top line of the status screen alternates with the
warning type. The lower line continues to display current and temperature
information: