INSTALLATION: INSTALLATION
MVS Series
11
710-03261-00D
Installation
4
4.1
Mounting Instructions - Power Assembly
All MVS models have an IP00 rating and must be installed inside an enclosure.
The power assembly should be installed with 100 mm clearance above for
isolation. No clearance is required below or at the sides.
min 100 mm (3.93 inch)
The power assembly is mounted in place using four M12 bolts. One bolt is
required through each corner at the base of the unit, tightened to a torque of
40 Nm. Individual phase arms are secured within the frame using three M10 bolts,
tightened to a torque of 17 Nm.
Front of Unit
A
To suit M12 mounting bolt
Horizontal Cross-section
A
mm (inch)
B
mm (inch)
C
mm (inch)
MVSxxxx-V02
MVSxxxx-V03
MVSxxxx-V04
636
(25.04)
513
(20.20)
68.5
(2.70)
MVSxxxx-V06
MVSxxxx-V07
842
(33.15)
663
(26.10)
68.5
(2.70)
MVSxxxx-V11
Contact your local supplier.
Chapter 4