OPERATION: USER INTERFACE
710-03261-00D 34
MVS
Series
8.6 Programming
Menu
The Programming Menu provides access to programmable parameters.
To open the Programming Menu, press the
►
button while viewing the metering
screens.
Items in the Programming Menu are grouped into sets of related parameters. Use
the
▲
and
▼
buttons to move between parameters groups and between the
parameters in each group.
The security access code must be entered to access parameters in parameter
group 20 or higher.
Parameter Group
Parameters
Primary Motor Settings
1-A Motor Full Load Current
1-B Motor Maximum Start Time
1-C Motor Locked Rotor Current
1-D Motor Service Factor
Start/Stop Modes-1
2-A Start Mode
2-B Current Limit
2-C Current Ramp – Initial Start Current
2-D Current Ramp – Start Ramp Time
2-E Kickstart Current Level
2-F Kickstart Duration
2-G Excess Start Time
2-H Stop Mode
2-I Soft Stop Ramp Time
Protection Settings
3-A Undercurrent Level
3-B Undercurrent Trip Delay
3-C Instantaneous Overcurrent Level
3-D Instantaneous Overcurrent Trip Delay
3-E Current Imbalance Level
3-F Current Imbalance Trip Delay
3-G Phase Sequence
3-H Mains Frequency Trip Mode
3-I Mains Frequency Trip Range
3-J Mains Frequency Trip Delay
3-K Restart Delay
3-L Restart Temperature Check
3-M Auxiliary Trip A – Mode
3-N Auxiliary Trip A – Delay
3-O Auxiliary Trip A – Enable Delay
3-P Auxiliary Trip B – Mode
3-Q Auxiliary Trip B – Delay
3-R Auxiliary Trip B – Enable Delay
3-S Ground Fault Level
3-T Ground Fault Trip Delay
3-U Overvoltage Level
3-V Overvoltage Trip Delay
3-W Undervoltage Level
3-X Undervoltage Trip Delay
Inputs
4-A Local/Remote Control
4-B Serial Control – Remote Mode
4-C Input A Functionality
4-D Input B Functionality