INTRODUCTION: SPECIFICATIONS
MVS Series
9
710-03261-00D
Outputs
Relay Outputs .............................................................. 10 A @ 250 VAC/ 360 VA
10 A @ 30 VDC resistive
Main Contactor (Terminals 13, 14) ............................................... Normally Open
Bypass Contactor (Terminals 23, 24) ........................................... Normally Open
Run Output/ PFC (Terminals 33, 34) ............................................ Normally Open
Output Relay A (Terminals 43, 44) ............................................... Normally Open
Output Relay B (Terminals 51, 52, 54) ............................................ Changeover
Output Relay C (Terminals 61, 62, 64) ............................................. Changeover
Analog Output (Terminals B10, B11) ................................... 0-20 mA or 4-20 mA
Environmental
Degree of Protection
Power Assembly ...................................................................................... IP00
Controller
............................................................................... IP54/ NEMA 12
Operating Temperature ............................................................. - 10
˚
C to + 60
˚
C
Storage Temperature ................................................................ - 25
˚
C to + 55
˚
C
- 25
˚
C to + 70
˚
C (< 24 hours)
Humidity ................................................................ 5% to 95% Relative Humidity
Pollution Degree ...................................................................... Pollution Degree 3
Vibration ............................................ Designed to IEC 60068 Test Fc Sinusoidal
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment Class (EMC) ............................................................................ Class A
Conducted Radio Frequency Emission ...... 10 kHz to 150 kHz: < 120 - 69 dB µV
0.15 MHz to 0.5 MHz: < 79 dB µV
0.5 MHz to 30 MHz: < 73 dB µV
Radiated Radio Frequency Emission ...... 0.15 MHz to 30 MHz: < 80-50 dB µV/m
30 MHz to 100 MHz: < 60-54 dB µV/m
100 MHz to 2000 MHz: < 54 dB µV/m
This product has been designed for Class A equipment. Use of the product in
domestic environments may cause radio interference, in which case the user may
be required to employ additional mitigation methods.
EMC Immunity
Electrostatic Discharge ..................... 6 kV contact discharge, 8 kV air discharge
Radio Frequency Electromagnetic Field ................ 80 MHz to 1000 MHz: 10 V/m
Fast Transients 5/50 ns (main and control circuits) .................................................
2 kV line to earth, 1 kV line to line
Surges 1.2/50 µs (main and control circuits) .. 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ............ 5000 ms (at 0% nominal voltage)
(safe shutdown)
Short Circuit
Rated short-circuit current, symmetrical, fused (Class E2)
MVSxxxx-V02-xxx ~ MVSxxxx-V07-xxx ................................................ 48 kA
MVSxxxx-V11-xxx ................................................................................... TBA
Heat Dissipation (Steady State)
Power Assembly (SCRs bypassed) ................................................. 20 W approx
Controller ........................................................................................... 10 W approx
Standards Approvals
C
9
........................................................................................ EMC requirements
UL/ C-UL ...................................................................................... UL 508, UL 347
CE ......................................................................................... EMC EU Directive
Marine ...................................................................................................... pending