29
terminal machine to communicate with mass data of the instrument. Besides, optical network can be adopted to
realize communication when the communication distance exceeds 300 m. Ethernet communication can be realized
in the system configuration of the recorder with IP address selected and relevant setting made in the software for
computer management.
Refer to Tables 1 and 2 for the specific parameters.
Table 1 Table of the Corresponding Input Register Address of 0 * 04 Read Command
No.
Input Register Address
(Decimal System)
Parameter Name
Data Format
Type
Remarks
Dynamic variables
1
00
Measured value of channel 1
Float
Read only
2
02
Measured value of channel 2
Float
Read only
……
……
……
Float
Read only
n
2(n-1)
Measured value of channel n
Float
Read only n: channel number
……
……
……
Float
Read only
59
116
Measured value of channel 59
Float
Read only
60
118
Measured value of channel 60
Float
Read only
61
120
Output state of contact
Long
Read only
Digits from 0 to 17
represent the output
states of the contacts
from
1
to
18
respectively, where
0 means "Off" and 1
means "Close".
In terms of the
address
120:00000000
00000000,
the
previous
digits,
from low to high,
represent the states
of alarms from 1 to
8 respectively, while
the latter digits,
from low to high,
represent the states
of alarms from 9 to
16 respectively;
The latter digits of
the previous digits
of
120:00000000
00000000, from low
to high, represent
the states of alarms
of the alarms 17 and
18 respectively.