Fault
code
Fault
description
Cause
Actions
0x2315
Motor
overcurrent
Short Circuit detected in U phase
Try to reset the error.
If error returns, contact Atlas Copco.
0x2316
Motor
overcurrent
Short Circuit detected in V phase
0x2317
Motor
overcurrent
Short Circuit detected in W phase
0x3210
Overvoltage
Overvoltage detected
Check if main supply voltage is within
specs. Check main fuses.
0x3221
Undervoltage
Main Power supply voltage too low.
0x3223
Undervoltage
Phase loss detected
0x3224
Overvoltage
Maximum allowable voltage of the DC-
link exceeded; Threshold is lowered in
case of higher temperature
Let drive cool off
Check for excessive ambient
temperature
Clean heatsink with compressed air
Clean inlet filter cubicle
Ensure proper flow of cooling air in
compressor room
Check if supply voltage is within
specs
0x3225
Undervoltage
Undervoltage detected
Check if main supply voltage is within
specs.
Check main fuses.
0x3226
Overvoltage
Overvoltage or overtemperature
detected in IGBT (U phase)
Let drive cool off.
Check for excessive ambient
temperature.
Clean heatsink with compressed air.
Clean inlet filter cubicle.
Ensure proper flow of cooling air in
compressor room.
Check if supply voltage is within
specs.
0x3227
Overvoltage
Overvoltage or overtemperature
detected in IGBT (V phase)
0x3228
Overvoltage
Overvoltage or overtemperature
detected in IGBT (W phase)
Instruction book
110