Condition
Possible cause
Remedy
Excessive oil consumption; oil
carry-over through discharge line
Incorrect oil causing foam
Change to correct oil
Oil level too high
Check for overfilling. Release
pressure and drain oil to correct
level.
Oil separator defective
Replace oil separator element
Malfunctioning of the scavenge
line
Replace non-return valve in the
scavenge line
Faults and remedies, dryer
For all references hereafter, consult section
.
Condition
Fault
Remedy
Pressure dew point too high
Air inlet temperature too high
Check and correct; if necessary, clean the
aftercooler of the compressor
Ambient temperature too high Check and correct; if necessary, draw
cooling air via a duct from a cooler place or
relocate the compressor
Shortage of refrigerant
Have circuit checked for leaks and
recharged
Refrigerant compressor does
not run
See below
Evaporator pressure too high
See below
Condenser pressure too high
See below
Condenser pressure too high
or too low
Fan control switch out of
order
Replace
Fan blades or fan motor out of
order
Have checked fan/fan motor, if necessary
replace.
Ambient temperature too high Check and correct; if necessary, draw
cooling air via a duct from a cooler place or
relocate the compressor
Condenser externally clogged Clean condenser
Compressor stops or does not
start
Electric power supply to
compressor is interrupted
Check and correct as necessary
Thermal protection of
refrigerant compressor motor
has tripped
Motor will restart when motor windings have
cooled down
Electronic condensate drain
remains inoperative
Electronic drain system
clogged
Have system inspected
Clean the filter of the automatic drain by
opening the manual drain valve. Check
functioning of the drain by pushing the test
button.
Condensate trap continuously
discharges air and water
Automatic drain out of order
Have system checked. If necessary,
replace the automatic drain.
Evaporator pressure is too
high or too low at unload
Hot gas bypass valve
incorrectly set or out of order
Have hot gas bypass valve adjusted
Instruction book
API480496
107
Summary of Contents for GA 37 VSD
Page 1: ...INSTRUCTION BOOK API480496 GA 37 VSD ...
Page 2: ......
Page 14: ...Front view GA 37 VSD up to GA 45 VSD Workplace Full Feature Instruction book 12 API480496 ...
Page 127: ......