Relay Output Modes define how the relay outputs will work. There are four different Relay Output Modes:
“
Hys
”, “
band
”, “
dose
” and “
pLvraL
”.
“
HYS
” is the default Mode for all relay outputs. In this Mode, Hysteresis is active (see 4.2.2 Setting
Hysteresis p. 12), and relays will switch at their corresponding Set Values plus Hysteresis values.
“
band
” Mode defines a bandwidth where the relay will be switched. Outside that bandwidth the relay
output will be in its default position. When “
band
” Mode is selected, corresponding Set Value Menu will
ask you two parameters to define the bandwidth, a lower and an upper limit. For example, if you define
“
type-1
” as “
band
”, then the relay at OUT-‐1 will be in “
band
” Mode. Therefore “
SET-1
“ menu will ask
you to enter “
fron-1
”(lower limit) and “
to-1
”(upper limit) parameters. The relay at OUT-‐1 will be
switched between “
Fron-1
” up until “
to-1
” value. Outside that range, the relay will be in its default
position.
“
dose
” Mode will change the output of the relay at the multiples of the corresponding Set Value. For
example if you define “
type-2
” as “
dose
”, the relay at OUT-‐2 will be in “
dose
” Mode. If you enter “
SET-
2
” as “
5
”, the relay at OUT-‐2 will switch at 5, 10, 15, 20…. The relay will stay switched for the time period
defined in “
t-Ovt2
” (see 4.2.4 Setting Relay Output Time p. 14).
“
pLvraL
” is only available for “
type-1
”, so you can use this Mode only for relay at OUT-‐1. You can define
10 different Set Values for OUT-‐1 relay. The relay will switch when the value on the display reaches to one
of the defined Set Values for the time period defined in “
t-Ovt1
” (see 4.2.4 Setting Relay Output Time p.
14).
In order to select Relay Output Modes, you should first enter to Setting Menu by pressing PRG ( ) and
UP ( ) buttons. The display will show the first submenu in Setting Menu, “
INPvT
”. Output Menu is the
second submenu in Setting Menu, so press UP ( ) button, and the display will show “
Ovtpvt
”. Press PRG
( ) button to enter Output Menu. Relay Output Modes are selected for each relay separately through
“
type-1
”, “
type-2
” and “
type-3
” parameters, which are sixth, seventh and eighth in the Output Menu.
Press UP ( ) button 5 times to reach the sixth parameter in Output Menu, which is “
type-1
”. Press PRG
( ) button to see the current setting of the Relay Output Mode for OUT-‐1 relay. In order to change the
Mode, press PRG ( ) button again, and the display will start flashing. Use UP ( ) and DOWN ( )
buttons to navigate inside the menu, and press PRG ( ) button to save the Mode. If you want to exit
without saving, press ESC ( ) button.
4.2.3.
Relay Output Mode
(type)
Type-1
Hys
Type-2
dose
band
pLvral
Type-3
prog
˝Ovtpvt
˝Inpvt
x5
...
Output Menu
...
Relay Output Modes