[11]
There are three output relays in ALP-‐94 (optionally 4 relays). Each output relay has a Set Value parameter.
So there are three Set Value parameters, namely “
Set-1
”, “
Set-2
” and “
Set-3
”. Output relays are
numbered according to the connection diagram on page 3. “
Set-1
” is the Set Value of the relay at OUT-‐1.
“
Set-2
” is the Set Value of the relay at OUT-‐2, and “
Set-3
” is the Set Value of the relay at OUT-‐3. If the
value on the display is equal to a Set Value, the corresponding relay switches and corresponding status LED
will be ON.
In order to enter Set Values, you should first enter to Setting Menu by pressing PRG ( ) and UP ( )
buttons. First submenu in the Setting Menu is Input Menu, so the display will show “
INPUT
”. Output Menu
is the second submenu in Setting Menu, so press UP ( ) button, and the display will show “
Ovtpvt
”.
Press PRG ( ) button to enter Output Menu, and the display will show “
SET-1
”. First three items in the
Output Menu are “
SET-1
”, “
SET-2
”, and “
SET-3
”. Scroll up or down to the Set Value you want to enter,
by using UP ( ) and DOWN ( ) buttons. Then press PRG ( ) button in order to enter the Set Value
parameter. The display will show the current Set Value parameter. In order to change it press PRG ( )
button again, and the rightmost digit will start flashing. While the rightmost digit is flashing, use UP ( )
and DOWN ( ) buttons to increase or decrease that digit. Press LEFT ( ) button to change the next
digit. Once you entered the value you want for that Set Value, press PRG ( ) button to save it. If you
want to exit without saving, press ESC ( ) button.
4.2. OUTPUT MENU
4.2.1.
Entering Set Value
(set)
prog
˝Ovtpvt
set-1
10
set-2
Use UP and DOWN buttons
to increase the flashing
digit, and use LEFT button
to go to next digit.
set-3
Output Menu
set-1 set-2 set-3 Hys-vp Hys-dn Type-1 Type-2
Type-3 T-ovt1 t-ovt2 t-ovt3 decpnt rate
prog
˝Inpvt
˝Ovtpvt
Output Menu
˝Inpvt
...
Output Menu
Set Value Parameter