4x1,5 mm²
H05V2V2-F
2 phases, 1 neutral conductor
2x06A
5x1,5 mm²
H05V2V2-F
2 phases, 2 neutral conductors
(only for NL)
2x16A
4x4,0 mm²
H05V2V2-F
2 phases, 1 neutral conductors
2x32A
3x6,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x48A
3x6,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x35A
3x4,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x32A
3x4,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x25A
3x4,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x20A
3x4,0 mm²
H05V2V2-F
1 phase, 1 neutral conductor
1x16A
The following connections are possible.
1 phase, 1 neutral conductor (220–240 V~, 50-60 Hz).
To reach the rated maximum power a fuse of 48A is needed.
Install a jumper between terminals 1 and 2, between terminals 2 and 3
and between terminals 4 and 5.
2 phases, 1 neutral conductor (380–415 V 2N~, 50-60 Hz).
To reach the rated maximum power two fuses of 32A are needed.
Install a jumper between terminals 2 and 3 and between terminals 4
and 5.
3 phases, 1 neutral conductor (380–415 V 3N ~, 50-60 Hz).
To reach the rated maximum power three fuses of 16A are needed.
Install a jumper between terminals 4 and 5.
55
Electrical installation