Astraada DRV-22 inverters Appendix C
79
C.6.3 C2 Filter type instruction
AS20FL I 4 016
A
B C D
Character
designation
Detailed instruction
A
FLT:inverter filter series
B
Filter type
P:power supply filter
L:output filter
C
Voltage degree
2
:
AC 1PH 220V(-15%)~240V(+10%)
4: AC 3PH 380V (-15%)~440V(+10%)
D
3 bit rated current code “016” means 16A
C.6.3 C2 filter
Model
Input filter
Output filter
AS22DRV20C4
AS20FLI2010
AS20FLU2010
AS22DRV20C7
AS20FLI2010
AS20FLU2010
AS22DRV21C5
AS20FLI4016
AS20FLU4016
AS22DRV22C2
AS20FLI4032
AS20FLU4032
AS22DRV40C7
AS20FLI4006
AS20FLU4006
AS22DRV41C5
AS20FLI4006
AS20FLU4006
AS22DRV42C2
AS20FLI4010
AS20FLU4010
Note:
1. The input EMI meet the requirement of C2 after adding input filters.
2. Above options are external, the customer should indicate when purchasing.
C.7 Braking components
C.7.1 Select the braking components
It is appropriate to use braking resistor or braking unit when the motor brakes sharply or the motor is driven by a high inertia load. The motor will become a
generator if its actual rotating speed is higher than the corresponding speed of the reference frequency. As a result, the inertial energy of the motor and load
return to the inverter to charge the capacitors in the main DC circuit. When the voltage increases to the limit, damage may occur to the inverter. It is necessary to
apply braking unit/resistor to avoid this accident happens.
Only qualified electricians are allowed to design, install, commission and operate
on the inverter.
Follow the instructions in “warning” during working. Physical injury or death or
serious property may occur.
Only qualified electricians are allowed to wire. Damage to the inverter or braking
options and part may occur. Read carefully the instructions of braking resistors or
units before connecting them with the inverter.
Do not connect the braking resistor with other terminals except for PB and
(
-
)
. Do
not connect the braking unit with other terminals except for
(
+
)
and
(
-
)
.Damage
to the inverter or braking circuit or fire may occur.
Connect the braking resistor or braking unit with the inverter according to the
diagram. Incorrect wiring may cause damage to the inverter or other devices.
Astraada DRV-22 series inverters have internal braking units.
Model
Type of
braking unit
Braking
resistor at
100% of
the braking
torque (
Ω
)
The consumed power of the braking resistor
Min.
braking
resistor
(
Ω
)
10% braking 50% braking 80% braking
AS22DRV20C4
Internal braking
unit
361
0.06
0.30
0.48
42
AS22DRV20C7
192
0.11
0.56
0.90
42
AS22DRV21C5
96
0.23
1.10
1.80
30
AS22DRV22C2
65
0.33
1.70
2.64
21
AS22DRV40C7
653
0.11
0.56
0.90
100
AS22DRV41C5
326
0.23
1.13
1.80
100
AS22DRV42C2
222
0.33
1.65
2.64
54
Note: