Astraada DRV-22 inverters Keypad operation procedure
17
Figure 4-5 Sketch map of state watching
5 Function Parameters
The function parameters of Astraada DRV-22 series inverters have been divided into 30 groups (P00~P29) according to the function, of which P18~P28 are
reserved. Each function group contains certain function codes applying 3-level menus. For example, “P08.08” means the eighth function code in the P8 group
function, P29 group is factory reserved, and users are forbidden to access these parameters.
For the convenience of function codes setting, the function group number corresponds to the first level menu, the function code corresponds to the second level
menu and the function code corresponds to the third level menu.
1. Below is the instruction of the function lists:
The first column “Function code”:codes of function parameter group and parameters
;
The second column “Name”:full name of function parameters
;
The third column “Detailed illustration of parameters”:Detailed illustration of the function parameters
The fourth column “Default value”:the original factory set value of the function parameter
;
The fifth column “Modify”: the modifying character of function codes (the parameters can be modified or not and the modifying conditions),below is the
instruction:
“
○
”: means the set value of the parameter can be modified on stop and running state
;
“
◎
”: means the set value of the parameter can not be modified on the running state
;
“
●
”: means the value of the parameter is the real detection value which can not be modified.
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00 Group Basic function group
P00.00
Speed control
mode
0: SVC 0
.No need to install encoders. Suitable in applications which
need low frequency, big torque for high accuracy of rotating
speed and torque control. Relative to mode 1, it is more
suitable for the applications which need small power.
1: SVC 1
1 is suitable in high performance cases with the advantage
of high accuracy of rotating speed and torque. It does not
need to install pulse encoder.
2:SVPWM control
2 is suitable in applications which do not need high control
accuracy, such as the load of fan and pump. One inverter
can drive multiple motors.
1
◎
P00.01
Run command
channel
Select the run command channel of the inverter.
The control command of the inverter includes: start, stop,
forward/reverse rotating, jogging and fault reset.
0:Keypad running command channel (“LOCAL/REMOT”
light off)
Carry out the command control by RUN, STOP/RST on the
keypad.
Set the multi-function key QUICK/JOG to FWD/REVC
shifting function (P07.02=3) to change the running direction;
press RUN and STOP/RST simultaneously in running state
to make the inverter coast to stop.
1:Terminal running command channel (“LOCAL/REMOT”
flickering)
Carry out the running command control by the forward
rotation, reverse rotation and forward jogging and reverse
jogging of the multi-function terminals
2:Communication running command channel
(“LOCAL/REMOT” on);
The running command is controlled by the upper monitor via
communication
0
○
P00.03
Max. output
This parameter is used to set the maximum output
50.00Hz
◎