Astraada DRV-22 inverters Function Parameters
33
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.14
S1 terminal
switching on
delay time
The function code defines the corresponding delay time of
electrical level of the programmable terminals from
switching on to switching off.
Setting range:0.000~50.000s
0.000s
○
P05.15
S1
terminal
switching off
delay time
0.000s
○
P05.16
S2 terminal
switching on
delay time
0.000s
○
P05.17
S2
terminal
switching off
delay time
0.000s
○
P05.18
S3 terminal
switching on
delay time
0.000s
○
P05.19
S3
terminal
switching off
delay time
0.000s
○
P05.20
S4 terminal
switching on
delay time
0.000s
○
P05.21
S4
terminal
switching off
delay time
0.000s
○
P05.30
HDI
terminal
switching on
delay time
0.000s
○
P05.31
HDI
terminal
switching off
delay time
0.000s
○
P05.32
Lower limit of
AI1
AI1 is set by the analog potentiometer, AI2 is set by control
terminal AI2 and AI3 is set by control terminal AI3. The
function code defines the relationship between the analog
input voltage and its corresponding set value. If the analog
input voltage beyond the set minimum or maximum input
value, the inverter will count at the minimum or maximum
one.
When the analog input is the current input, the
corresponding voltage of 0~20mA is 0~10V.
In different cases, the corresponding rated value of 100.0%
is different. See the application for detailed information.
The figure below illustrates different applications:
Input filter time: this parameter is used to adjust the
0.00V
○
P05.33
Corresponding
setting of the
lower limit of
AI1
0.0%
○
P05.34
Upper limit of
AI1
10.00V
○
P05.35
Corresponding
setting of
the upper limit
of AI1
100.0%
○
P05.36
AI1 input filter
time
0.100s
○
P05.37
Lower limit of
AI2
0.00V
○
P05.38
Corresponding
setting of the
lower limit of
AI2
0.0%
○
P05.39
Upper limit of
AI2
10.00V
○