ASENWARE LTD.
20
2.3.3.1
Action to Fault Event
When a fault incident occurs, the operator must take action to respond to fire alarm :
-
Silence the Panel sounder :
By pressing the soft key
Panel Buzzer Silence
, the local sounder
will silence and the Fire Alarm LED will change from flashing to steady. By pressing this, panel
will acknowledge the signal to panel screen, history buffer, printer and annunciator, if installed.
- Check the trouble message on the display screen and refer Table 2.1 and Table 2.2 for its
explanation , if necessary.
- Correct the condition which causing the fault.
- If all troubles clear and no supervisory signals or fire alarms exist, the control panel returns to
normal condition automatically and send the message to history buffer, printer and annunciator, if
installed.
2.3.3.2
Types of Fault
There are many types of fault signal which gives message on the screen, here they are describes
as point fault and system fault. Table 2.1 and Table 2.2 summarize some troubles which will
appear on the screen when any of fault incident occurs.
Table 2.1 Point Fault
FAULT TYPE
DESCRIPTION
ACTION
Earth Fault
Panel Earth Fault in DC supply
correct the fault
AC Failure
The main or auxiliary AC power failure Determine if its AC power loss or
wiring connection
Battery Fault
Any failure in battery and battery
charger when it can not charge the
battery
Check for batteries if it need to be
replaced. If charger is drawing
enough current to charge.
Fire Routing Fault
Fire routing wiring connection open
Check and correct
Fire routing wiring connection short
Fault Routing Fault
Fault routing wiring connection open
Check and correct
Fault routing wiring connection short
Evacuation Fault
Evacuate output open
Check and correct
Evacuate output short
Device (Address) Fault
Any type of fault i.e. open, short ,
communication etc. occurs in any
devices e.g. detectors , modules etc.
Check the connections from the
module to the input or output device
to which it is wired.
Summary of Contents for Addressable Fire Alarm Control Panel
Page 32: ...ASENWARE LTD 32 Figure 3 10 TCP IP Address Window Screen Figure 3 11 CAN Window Screen ...
Page 37: ...37 Figure 3 17 User List Figure 3 18 User Access Chart ...
Page 50: ...50 ASENWARE LTD All dimensions are in mm ...
Page 52: ...52 ASENWARE LTD All dimensions are in mm Same size of box is supplied for all type of modules ...
Page 54: ...54 ASENWARE LTD Wiring Connection ...
Page 56: ...56 ASENWARE LTD Wiring Connection ...
Page 58: ...58 ASENWARE LTD Wiring Connection ...
Page 62: ...62 ASENWARE LTD All dimensions are in mm ...
Page 66: ......