48
ACK-E-2009
Engineering & Physical Data
General Data - Cooling Only (R410A)
MODEL
INDOOR UNIT
A5CK 50E
OUTDOOR UNIT
A5LC 50C
NOMINAL CAPACITY
Btu/h
43000
W
12603
NOMINAL TOTAL INPUT POWER
W
4390
NOMINAL RUNNING CURRENT
A
7.6
POWER SOURCE
V/Ph/Hz
380 - 415 / 3 / 50
EER
W/W
2.87
REFRIGERANT TYPE
R410A
REFRIGERANT CONTROL (EXPANSION DEVICE)
OUTDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
OPERATION
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
AIR FLOW
HIGH
l/s / CFM
570 / 1200
MEDIUM
l/s / CFM
490 / 1030
LOW
l/s / CFM
440 / 930
EXTERNAL STATIC PRESSURE (H/M/L)
Pa (in.wg.)
0
SOUND PRESSURE LEVEL (H/M/L)
dBA
47 / 44 / 43
UNIT DIMENSION
( ) - WITH PANEL
HEIGHT
mm/in
300 (375) / 11.81 (14.76)
WIDTH
mm/in
820 (990) / 32.3 (38.98)
DEPTH
mm/in
820(990) / 32.3 (38.98)
PACKING DIMENSION
( ) - PANEL
HEIGHT
mm/in
335 (110) / 13.19 (4.3)
WIDTH
mm/in
916 (1030) / 36.1 (40.6)
DEPTH
mm/in
916 (1030) / 36.1 (40.6)
WEIGHT (UNIT + PANEL)
kg/lb
42+6 / 92.6+13.2
CONDENSATE DRAIN SIZE
mm/in
19.1 / 0.75
OUTDOOR UNIT
AIR FLOW
l/s / CFM
2171 / 4600
SOUND PRESSURE LEVEL
dBA
68
UNIT DIMENSION
HEIGHT
mm/in
850 / 33.46
WIDTH
mm/in
1030 / 40.55
DEPTH
mm/in
400 / 15.75
PACKING DIMENSION
HEIGHT
mm/in
1000 / 39.37
WIDTH
mm/in
1200 / 47.24
DEPTH
mm/in
560 / 22.05
UNIT WEIGHT
kg/lb
105 / 231.5
PIPE CONNECTION
TYPE
FLARE VALVE
SIZE
LIQUID
mm/in
9.5 / 3/8
GAS
mm/in
15.9 / 5/8
REFRIGERANT CHARGE
kg/lb
2.3 / 5.07
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL SPECIFICATIONS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.5m BELOW FASCIA.
07-General data_A.indd 48
07-General data_A.indd 48
4/6/2009 11:13:10 AM
4/6/2009 11:13:10 AM