107
Electrical Data
ACK-E-2009
Electrical Data - Heat Pump (R22)
MODEL
INDOOR UNIT
ACK 40ER
ACK 40ER
OUTDOOR UNIT
ALC 35CR
ALC 40CR
INDOOR MOTOR
INSULATION GRADE
CLASS B
CLASS B
POWER SOURCE
V/Ph/Hz
220 - 240 / 1 / 50
220 - 240 / 1 / 50
RATED INPUT POWER
W
176
176
RATED RUNNING CURRENT
A
0.79
0.79
MOTOR OUTPUT
W
60
60
POLES
6
6
OUTDOOR MOTOR
INSULATION GRADE
CLASS B
CLASS B
POWER SOURCE
V/Ph/Hz
220 - 240 / 1 / 50
220 - 240 / 1 / 50
RATED INPUT POWER
W
220
220
RATED RUNNING CURRENT
A
1.02
1.02
MOTOR OUTPUT
W
145
145
POLES
8
8
COMPRESSOR
INSULATION GRADE
-
-
POWER SOURCE - 1Ø / <3Ø>
V/Ph/Hz
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
220 - 240 / 1 / 50 /
<380 - 415 / 3 / 50>
CAPACITOR - 1Ø / <3Ø>
μ
F
60
60 / <NIL>
RATED INPUT POWER (COOLING) - 1Ø / <3Ø>
W
2614
3054 / <2864>
RATED INPUT POWER (HEATING) - 1Ø / <3Ø>
W
2354
2854 / <2804>
RATED RUNNING CURRENT (COOLING) -
1Ø / <3Ø>
A
12.6
14.9 / <5.2>
RATED RUNNING CURRENT (HEATING) -
1Ø / <3Ø>
A
11.6
14.1 / <5.4>
LOCKED ROTOR AMP. - 1Ø / <3Ø>
A
114
114 / <48>
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
MODEL
INDOOR UNIT
ACK 50ER
OUTDOOR UNIT
ALC 50CR
INDOOR MOTOR
INSULATION GRADE
CLASS B
POWER SOURCE
V/Ph/Hz
220 - 240 / 1 / 50
RATED INPUT POWER
W
221
RATED RUNNING CURRENT
A
0.97
MOTOR OUTPUT
W
100
POLES
6
OUTDOOR MOTOR
INSULATION GRADE
CLASS B
POWER SOURCE
V/Ph/Hz
220 - 240 / 1 / 50
RATED INPUT POWER
W
220
RATED RUNNING CURRENT
A
1.02
MOTOR OUTPUT
W
145
POLES
8
COMPRESSOR
INSULATION GRADE
-
POWER SOURCE
V/Ph/Hz
380 - 415 / 3 / 50
CAPACITOR
μ
F
NIL
RATED INPUT POWER (COOLING)
W
4159
RATED INPUT POWER (HEATING)
W
3629
RATED RUNNING CURRENT (COOLING)
A
7.3
RATED RUNNING CURRENT (HEATING)
A
6.5
LOCKED ROTOR AMP.
A
56
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
10_Electrical Data_A.indd 107
10_Electrical Data_A.indd 107
4/6/2009 3:41:28 PM
4/6/2009 3:41:28 PM