39
Engineering & Physical Data
ACK-E-2009
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT
ACK 40E
ACK 40E
OUTDOOR UNIT
ALC 35C
ALC 40C
NOMINAL CAPACITY - 1Ø <3Ø>
Btu/h
35000
39000 <40000>
W
10258
11430 <11723>
NOMINAL TOTAL INPUT POWER - 1Ø <3Ø>
W
3010
3450 <3260>
NOMINAL RUNNING CURRENT - 1Ø <3Ø>
A
14.4
16.7 <5.8>
POWER SOURCE - 1Ø <3Ø>
V/Ph/Hz
220 - 240 / 1 / 50
220 - 240 / 1 / 50
<380 - 415 / 3 / 50>
EER - 1Ø <3Ø>
W/W
3.41
3.31 / <3.59>
REFRIGERANT TYPE
R22
R22
REFRIGERANT CONTROL (EXPANSION DEVICE)
INDOOR CAP. TUBE
INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
4 WAY AUTOMATIC LOUVER
(UP & DOWN)
OPERATION
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
WIRELESS OR WIRED MICRO-
COMPUTER REMOTE CONTROL
AIR FLOW
HIGH
l/s / CFM
490 / 1030
490 / 1030
MEDIUM
l/s / CFM
410 / 860
410 / 860
LOW
l/s / CFM
350 / 740
350 / 740
EXTERNAL STATIC PRESSURE (H/M/L)
Pa / in.wg.
0
0
SOUND PRESSURE LEVEL (H/M/L)
dBA
44 / 41 / 38
44 / 41 / 38
UNIT DIMENSION
( ) - WITH PANEL
HEIGHT
mm/in
300 (375) / 11.81 (14.76)
300 (375) / 11.81 (14.76)
WIDTH
mm/in
820 (990) / 32.3 (38.98)
820 (990) / 32.3 (38.98)
DEPTH
mm/in
820 (990) / 32.3 (38.98)
820 (990) / 32.3 (38.98)
PACKING DIMENSION
( ) - PANEL
HEIGHT
mm/in
335 (110) / 13.19 (4.3)
335 (110) / 13.19 (4.3)
WIDTH
mm/in
916 (1030) / 36.1 (40.6)
916 (1030) / 36.1 (40.6)
DEPTH
mm/in
916 (1030) / 36.1 (40.6)
916 (1030) / 36.1 (40.6)
UNIT WEIGHT (UNIT + PANEL)
kg/lb
42+6 / 92.6+13.2
42+6 / 92.6+13.2
CONDENSATE DRAIN SIZE
mm/in
19.1 / 0.75
19.1 / 0.75
OUTDOOR UNIT
AIR FLOW
l/s / CFM
1605 / 3400
1605 / 3400
SOUND PRESSURE LEVEL
dBA
58
58
UNIT DIMENSION
HEIGHT
mm/in
850 / 33.5
850 / 33.5
WIDTH
mm/in
1030 / 40.6
1030 / 40.6
DEPTH
mm/in
400 / 15.8
400 / 15.8
PACKING DIMENSION
HEIGHT
mm/in
1000 / 39.4
1000 / 39.4
WIDTH
mm/in
1200 / 47.2
1200 / 47.2
DEPTH
mm/in
560 / 22.1
560 / 22.1
UNIT WEIGHT
kg/lb
95 / 209
100 / 221
PIPE CONNECTION
TYPE
FLARE VALVE
FLARE VALVE
SIZE
LIQUID
mm/in
9.5 / 3/8
9.5 / 3/8
GAS
mm/in
19.1 / 3/4
19.1 / 3/4
REFRIGERANT CHARGE
kg/lb
2.7 / 5.95
2.95 / 6.50
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.5m BELOW FASCIA.
07-General data_A.indd 39
07-General data_A.indd 39
4/6/2009 11:13:07 AM
4/6/2009 11:13:07 AM