Ascon Tecnologic - Y39H Line - Operating Instructions - Pag. 14

8  PROBLEMS AND MAINTENANCE

8.1 

Error messages

Error

Reason

Action

E1

The TRH probe (humidity and 

temperature) is not connected, 

in error or measures a value 

outside the allowed range

Check the correct connec-

tion of the probe with the 

instrument and check the 

probe works correctly

E2

 

-E2

The 

Pr2

 probe may be inter-

rupted (E) or in short circuit 

(-E), or may measure a value 

outside the range allowed

EPr

Internal EEPROM memory 

error (parameters checksum 

error)

Press the   key

Err

Fatal memory error 

Replace the instrument or 

ship to factory for repair

8.2 

Other messages

Message

Reason

od

Delay at power-on in progress

Ln

Keyboard lock

Hit

Maximum temperature alarm in progress

Lot

Minimum temperature alarm in progress

Hih

Maximum humidity alarm in progress

Loh

Minimum humidity alarm in progress

AL

Digital input alarm in progress

oP

Opern Door alarm

At

Autotunig running

Ats

Autotuning Start

AtE

Autotuning End

8.3 

Cleaning

We recommend  cleaning of the instrument only with a slightly 
wet cloth using water and not abrasive cleaners or solvents.

8.4 

Disposal

The appliance (or the product) must be disposed 

of separately in compliance with the local standards 

in force on waste disposal.

9  WARRANTY AND REPAIRS

The instrument is under warranty against manufacturing flaws or 
faulty material, that are found within 18 months from delivery date.
The guarantee is limited to repairs or to the replacement of 
the instrument. 
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty’s effects.
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales de-
partment to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alterna-
tive agreements.

10  TECHNICAL DATA

10.1  Electrical Data

Power supply: 12 VAC/DC, 12 ÷ 24 VAC/DC, 100 ÷ 240 VAC ±10%;
AC Frequency: 50/60 Hz;
Power consumption:

• 

12 V: 3 VA approx.;

• 

12... 24 VAC/VDC, 100... 240 VAC: 4 VA approx.;

• 

with ARS1: 5 VA approx.;

Inputs: 1 input for digital temperature and humidity probe TRH03 
1 usable for NTC temperature probe (103AT-2, 10 k

W

 @ 25 ° 

C) or alternatively as a digital input for voltage free contacts;
Output/s: up to 3 relay outputs

EN 61810 EN 60730 UL 60730

Out1

 (H) - SPST-NO - 16A -  

1HP 250V, 1/2HP 125 VAC

16 (9) A

10 (4) A

12 A Res.,  

30 LRA,  

5 FLA

Out1

 (Q) - SPST-NO 

SSR - 0.1... 2 A/250 VAC

-

-

-

Out2

 - SPDT - 8A - 1/2HP 250V, 

1/3HP 125 VAC

8 (3) A

4 (4) A

4 A Res.

Out3

 - SPST-NO - 5A -  

1/8HP 250V, 1/10HP 125 VAC

5 (2) A

2 (2) A

2 A Res.

16 A max. for common (pin. 1), 12 A max. for extractable 
terminal block model.
Electrical life for relay outputs: 100000 op. (EN60730);
Action type: type 1.B (EN 60730-1);
Overvoltage category: II;
Protection class: Class II;
Insulation: Reinforced insulation between the low voltage 
part (supply H type and relay output) and front panel; Re-
inforced insulation between the low voltage section (supply 
H type and relay output) and the extra low voltage section 
(inputs); Reinforced between supply and relay output; No 
insulation between supply F or G type and inputs.

10.2  Mechanical Data

Housing: Self-extinguishing plastic, UL 94 V0;
Heat and fire resistance category: D;
Ball Pressure Test (EN60730): accessible parts 75°C, sup-
port live parts 125°C;
Dimensions: 78 x 35 mm, depth 64 mm
Weight: 115 g approx.;
Mounting: Incorporated flush in panel  (thickness 12/29 mm 
max.) in 71 x 29 mm hole;
Connections:

• 

Power supply/Outputs: Screw terminals block or 
extractable screw terminals block or Faston for  
0.2 ÷ 2.5 mm

2

/AWG 24 ÷ 14 cables;

• 

Inputs: Screw terminals block or extractable screw 
terminals block 0.2 ÷ 2.5 mm

2

/AWG 24 ÷ 14 cables;

Front panel protection degree: IP65 (NEMA 3S) mounted 
with the optional screw type bracket;

Note: 

To order the optional screw type bracket, contact your 
local Ascon Tecnologic representative.

Pollution situation: 2;
Operating temperature: 0 ÷ 50°C;
Operating humidity: < 95 RH% with no condensation;
Storage temperature: -25 ÷ +60°C.

Summary of Contents for Y39H

Page 1: ...oling application with ON OFF control and humidity control humidification and deumidification with ON OFF control the instrument integrates an asymmetrical oscillator timer whitch can be used for spec...

Page 2: ...lashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 13 LED Tm Time When flashes points out that the twin timer which operates on the Auxiliay output is enabled 2 Progra...

Page 3: ...ly entering the password is protected if the SET LED is steady ON the parameter is programmable without password not protected To change the parameter visibility press the key and keep ing it pressed...

Page 4: ...insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree IP65 use the screw type bracket optional Avoid placing the instrument in env...

Page 5: ...obe Out2 Out1 Out3 TRH03 5 Functions 5 1 ON STAND BY Function Once powered the instrument can assume 2 different conditions ON The controller uses the control functions STAND BY The controller uses no...

Page 6: ...uration The instrument outputs can be configured by the relative pa rameters o o1 o o2 and o o3 The outputs can be configured for the following functions ot To manage the temperature control device In...

Page 7: ...ith neu tral zone r HC nr When r HC nr the output configured as ot operates with a cooling action like r HC C while the output configured as HE can be used to operate with a heating action The r d dif...

Page 8: ...the actuator motor or water injec tion solenoid valve 5 7 Compressor Protection Function and Delay at Power ON The compressor protection functions performed by the in strument are studied to avoid fre...

Page 9: ...AL A Lt A Ht A dt A dt time off off off ON ON Hit Lot Temp Pt or assume the values SP A Ht and SP A Lt if the alarms are relative A yt 2 AL A Lt SPt A Ht Temp Pt A dt A dt time off off off ON ON Hit L...

Page 10: ...uts are disabled at digital input intervention 5 8 4 Open Door Alarm The instrument can notify an Open door alarm activated by the digital input with the function programmed as i Fi 5 When the digital...

Page 11: ...PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please look at the A01 instruction manual 6 2 RS 485 Serial Interface by ARS1 Through the ARS1 device TTL RS485 interface and the ap p...

Page 12: ...th Humidity and Tempearture measurements alterna ted every 10 s tt Tempearture and countdown t of measurements alternated every 10 s 3U Humidity Tempearture and countdown t of mea surements alternated...

Page 13: ...h 0 0 30 0 RH 1 0 43 A th Humidity alarm delay A Hh and A Lh oF 0 01 9 59 min s 99 5 min s x 10 oF 44 A PA Temperature and Hunidity Alarms delay at power ON oF 0 01 9 59 h min 99 5 h min x 10 2 00 45...

Page 14: ...ithout any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 Technical Data 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50...

Page 15: ...EN61000 4 5 supply 2 kV com mode 1 kV diff mode EN61000 4 6 3 V 11 How to order MODEL Y39H Instrument with mechanical keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT...

Page 16: ...Ascon Tecnologic Y39H Line Operating Instructions Pag 16...

Reviews: