2.3 

Parameter Protection Using a Password

The instrument has a parameter protection function with 
password that can be customized using the parameter 

t.PP

.

To protect the parameters, set the desired Password Number 
at parameter 

tPP

.

When the protection is active, keep the   key pressed for 
about 5 s to access the parameters, the display shows 

r.p

.  

Press again the   key, the display changes to 

0

, now, using 

the  /  keys, insert the programmed password number 
and press the key   again.
If the password is correct the instrument displays the code of 
the first parameter and it will be possible to program the instru-
ment in the same way described in the previous paragraph.
The password protection can be disabled by setting 

t.PP

 = 

of

.

PARAMETERS

GROUP

(PROGRAM MODE)

INS. CORRECT

PASSWORD

0.

R.P.

-25.5

PASSWORD

REQUEST

s.lt.

NORMAL MODE

Hold

for 2 s

Hold for 5 s

Increase

Value

Decrease

Value

Notes:   1. 

All parameters are configured by default as “

pro-

tected by password

” so that by simply setting the 

t.PP

 parameter they are all password protected.

2. 

If the Password gets lost, just switch OFF and ON 
the instrument power supply, push   key during 
the initial test and keep it pressed for 5 seconds.  
In this way it is possible to have access to ALL the 
parameters, verify and modify the parameter 

t.PP

.

2.4 

Customized Mode Parameters Programming

 

(parameters programming level)

The instrument factory setting provide that the password protec-
tion acts on all parameters.  To make a parameter accessible 
without having to enter the password when 

t.PP

 password 

protection is active, use the procedure that follows:

 

Enter the Program mode using the 

t.PP

 Password and 

select the parameter that must always be accessible (no 
password protection).

 

Once the parameter has been selected, a 

blinking

 

SET

 LED 

means that the parameter can be programmed only entering 
the password (is protected), if the 

SET 

LED is 

steady ON

 the 

parameter is programmable without password (not protected).

 

To change the parameter visibility, press the   key and keep-
ing it pressed also press the   key.  The 

SET

 LED changes 

its state indicating the new access parameter level (

ON

 = not 

protected; 

blinking

 = protected by password). 

In case some parameters are not protected, accessing the 
the programming mode the display first shows the not pro-
tected parameters, then the 

r.p

 parameter (through which 

will be possible to access the “

protected

” parameters).

Previous

Parameter

Next

Parameter

SET

PARAMETER

Increase

Value

Decrease

Value

35.0

-25.5

NOT Protected

PARAMETERS

NORMAL MODE

Hold

for 2 s

Hold for 5 s

PARAMETERS

(PROGRAM MODE)

INS. CORRECT

PASSWORD

Increase

Value

Decrease

Value

0.

R.P.

PASSWORD

REQUEST

S.Lt.

a.Ht.

2.5 

Reset Parameters to Default Value

The instrument allows the reset of the parameters to those 
values programmed in factory as default.
To restore the default parameters value, set the value 

-48

 at 

r.p

 password request.

Therefore, to make the reset to the default parameters, ena-
ble the Password protection using the 

t.PP

 parameter so that 

the 

r.p

 setting is requested, at this point insert 

-48

 instead of 

the programmed access password.
Once confirmed the password with the   key, the display 
shows “

---

” for 2 s after which the instrument resets all the 

parameters to the factory default setting.

2.6 

Keyboard Lock function

The instrument allows to completely lock the keyboard.
This function is useful when the controller is installed in an 
accessible area and changes must be avoided.
To activate the keyboard lock, simply set the parameter 

t.Lo

 

to a value different than 

of

.

The 

t.Lo

 value is the keys inactivity time after which the in-

strument automatically locks the keyboard.  Therefore, press-
ing no buttons for the time set at 

t.Lo

, the normal functions 

of the keys are automatically disabled.
When the keyboard is locked, if any of the key is pressed, 
the display shows 

Ln

 to indicate that the lock is active.

To unlock the keyboard it is enough to contemporarily press 

 +   keys and keep them pressed for 5 s, after which the 

label 

LF

 appears on the display and all the key functions will 

be available again.

Summary of Contents for Y39H

Page 1: ...oling application with ON OFF control and humidity control humidification and deumidification with ON OFF control the instrument integrates an asymmetrical oscillator timer whitch can be used for spec...

Page 2: ...lashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 13 LED Tm Time When flashes points out that the twin timer which operates on the Auxiliay output is enabled 2 Progra...

Page 3: ...ly entering the password is protected if the SET LED is steady ON the parameter is programmable without password not protected To change the parameter visibility press the key and keep ing it pressed...

Page 4: ...insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree IP65 use the screw type bracket optional Avoid placing the instrument in env...

Page 5: ...obe Out2 Out1 Out3 TRH03 5 Functions 5 1 ON STAND BY Function Once powered the instrument can assume 2 different conditions ON The controller uses the control functions STAND BY The controller uses no...

Page 6: ...uration The instrument outputs can be configured by the relative pa rameters o o1 o o2 and o o3 The outputs can be configured for the following functions ot To manage the temperature control device In...

Page 7: ...ith neu tral zone r HC nr When r HC nr the output configured as ot operates with a cooling action like r HC C while the output configured as HE can be used to operate with a heating action The r d dif...

Page 8: ...the actuator motor or water injec tion solenoid valve 5 7 Compressor Protection Function and Delay at Power ON The compressor protection functions performed by the in strument are studied to avoid fre...

Page 9: ...AL A Lt A Ht A dt A dt time off off off ON ON Hit Lot Temp Pt or assume the values SP A Ht and SP A Lt if the alarms are relative A yt 2 AL A Lt SPt A Ht Temp Pt A dt A dt time off off off ON ON Hit L...

Page 10: ...uts are disabled at digital input intervention 5 8 4 Open Door Alarm The instrument can notify an Open door alarm activated by the digital input with the function programmed as i Fi 5 When the digital...

Page 11: ...PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please look at the A01 instruction manual 6 2 RS 485 Serial Interface by ARS1 Through the ARS1 device TTL RS485 interface and the ap p...

Page 12: ...th Humidity and Tempearture measurements alterna ted every 10 s tt Tempearture and countdown t of measurements alternated every 10 s 3U Humidity Tempearture and countdown t of mea surements alternated...

Page 13: ...h 0 0 30 0 RH 1 0 43 A th Humidity alarm delay A Hh and A Lh oF 0 01 9 59 min s 99 5 min s x 10 oF 44 A PA Temperature and Hunidity Alarms delay at power ON oF 0 01 9 59 h min 99 5 h min x 10 2 00 45...

Page 14: ...ithout any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 Technical Data 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50...

Page 15: ...EN61000 4 5 supply 2 kV com mode 1 kV diff mode EN61000 4 6 3 V 11 How to order MODEL Y39H Instrument with mechanical keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT...

Page 16: ...Ascon Tecnologic Y39H Line Operating Instructions Pag 16...

Reviews: