Parameter

Description

Range

Default

27 

r.dh

Humidity intervention differential (Hysteresis)

0.0 ÷ 30.0°C/°F

5.0

28 

r.h1

Humidity Output (

ot

) enable time for H. probe error

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

1.00

29 

r.h2

Humidity Output (

ot

) disable time for H. probe error

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

30 

r.ud

Humidity Output (

rh

) operating mode

u Humidifies;

d Dehumidifies;
nr 

Neutral zone (

rh

 = Dehumidifies, 

hu

 = Humidifies)

u

31 

P.t1

ot

 temperature control output activation delay

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s. x 10)

oF

32 

P.t2

ot

 temperature control output activation delay after 

ot

 

switch OFF

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

33 

P.od

Outputs activation delay at power ON

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

34 

A.yt

Temperature alarms type

Absolute with label (

Hit

 - 

Lot

) display;

Relative with label (

Hit

 - 

Lot

) display;

Absolute with no label display;

Relative with no label display.

1

35 

A.Ht

High temperature Alarm threshold

oF/-99.9 ÷ 999 °C/°F

oF

36 

A.Lt

Low temperature Alarm threshold

oF/-99.9 ÷ 999 °C/°F

oF

37 

A.dt

Temperature alarm differential 

A.Ht

 and 

A.Lt

0.0 ÷ 30.0°C/°F

1.0

38 

A.tt

Temperature alarm delay 

A.Ht

 and 

A.Lt

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

39 

A.yh

Humidity alarms type

Absolute with label (

Hih

 - 

Loh

) display;

Relative with label (

Hih

 - 

Loh

) display;

Absolute with no label display;

Relative with no label display.

1

40 

A.Hh

High humidity Alarm threshold

oF/-99.9 ÷ 100 RH%

oF

41 

A.Lh

Low humidity Alarm threshold

oF/-99.9 ÷ 100 RH%

oF

42 

A.dh

Humidity alarm differential 

A.Hh

 and 

A.Lh

0.0 ÷ 30.0 RH%

1.0

43 

A.th

Humidity alarm delay 

A.Hh

 and 

A.Lh

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

44 

A.PA

Temperature and Hunidity Alarms delay at power ON

oF/0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)

2.00

45 

A.oA

Alarm delay with door open

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

3.00

46 

o.o1

OUT1 function

oF 

No Function;

ot 

Temperature control (Cooling if 

r.HC

 = 

C

CP

nr

Heating if 

r.HC

 = 

H

 o 

HP

);

rh 

Humidity control (Dehumidification if 

r.ud

 = 

d

nr

Humidification if 

r.ud

 = 

u

);

HE 

Heating (with 

r.HC

 = 

nr

);

hu 

Humidification (with 

r.ud

 = 

nr

);

Au Auxiliary;

At/-t  Acknowledgeable alarm;

AL/-L  Not Acknowledgeable alarm;

on 

Output active when the instrument is ON;

L1 Light

ot

47 

o.o2

OUT2 function

rh

48 

o.o3

OUT3 function

Au

49 

o.bu

Buzzer function mode

oF Disabled;

Active alarms only;

Key pressed only;

Active alarms and key pressed.

3

50 

o.Fo

Auxiliary output operating mode

oF  No function;

Manual activation by key or digital input;

Independent twin timer;

Twin timer enabled only when the temperature 

control is disabled (when Temp. contr. enabled the 

output is always ON).

2

51 

o.tn

ON time relating to the auxiliary output

oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)

oF

52 

o.tF

OFF time relating to the auxiliary output

oF/0.01 ÷ 9.59 (min.s o h.min) ÷ 99.5 (min.s o h.min x 10) oF

53 

o.tu

Unità di misura parametro 

o.tF

H h.min;

n min.s.

n

54 

t.UF

 key operating mode

oF  No function;

Auxiliary output command;

Switch on/off (Stand-by)

Start Autotuning;

Light ON/OFF (

L1 

Output).

oF

55 

t.Fb

 key operating mode

oF

56 

t.Lo

Keyboard lock function delay

oF/0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10)

oF

57 

t.Ed

 key Fast Set Point change procedure; 

Setp Point visibility

oF None;

SPt

;

SPh

;

SPt

 and 

SPh

.

3

58 

t.PP

Access Password to parameter functions

oF ÷ 999

oF

59 

t.Ad

MODBUS address (serial communication)

0 ÷ 255

1

Summary of Contents for Y39H

Page 1: ...oling application with ON OFF control and humidity control humidification and deumidification with ON OFF control the instrument integrates an asymmetrical oscillator timer whitch can be used for spec...

Page 2: ...lashing 12 LED Stand By When the instrument is in Stand by mode is the only lit LED 13 LED Tm Time When flashes points out that the twin timer which operates on the Auxiliay output is enabled 2 Progra...

Page 3: ...ly entering the password is protected if the SET LED is steady ON the parameter is programmable without password not protected To change the parameter visibility press the key and keep ing it pressed...

Page 4: ...insert the instrument fixing it with the provided special brackets In order to obtain the declared front protection degree IP65 use the screw type bracket optional Avoid placing the instrument in env...

Page 5: ...obe Out2 Out1 Out3 TRH03 5 Functions 5 1 ON STAND BY Function Once powered the instrument can assume 2 different conditions ON The controller uses the control functions STAND BY The controller uses no...

Page 6: ...uration The instrument outputs can be configured by the relative pa rameters o o1 o o2 and o o3 The outputs can be configured for the following functions ot To manage the temperature control device In...

Page 7: ...ith neu tral zone r HC nr When r HC nr the output configured as ot operates with a cooling action like r HC C while the output configured as HE can be used to operate with a heating action The r d dif...

Page 8: ...the actuator motor or water injec tion solenoid valve 5 7 Compressor Protection Function and Delay at Power ON The compressor protection functions performed by the in strument are studied to avoid fre...

Page 9: ...AL A Lt A Ht A dt A dt time off off off ON ON Hit Lot Temp Pt or assume the values SP A Ht and SP A Lt if the alarms are relative A yt 2 AL A Lt SPt A Ht Temp Pt A dt A dt time off off off ON ON Hit L...

Page 10: ...uts are disabled at digital input intervention 5 8 4 Open Door Alarm The instrument can notify an Open door alarm activated by the digital input with the function programmed as i Fi 5 When the digital...

Page 11: ...PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please look at the A01 instruction manual 6 2 RS 485 Serial Interface by ARS1 Through the ARS1 device TTL RS485 interface and the ap p...

Page 12: ...th Humidity and Tempearture measurements alterna ted every 10 s tt Tempearture and countdown t of measurements alternated every 10 s 3U Humidity Tempearture and countdown t of mea surements alternated...

Page 13: ...h 0 0 30 0 RH 1 0 43 A th Humidity alarm delay A Hh and A Lh oF 0 01 9 59 min s 99 5 min s x 10 oF 44 A PA Temperature and Hunidity Alarms delay at power ON oF 0 01 9 59 h min 99 5 h min x 10 2 00 45...

Page 14: ...ithout any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 Technical Data 10 1 Electrical Data Power supply 12 VAC DC 12 24 VAC DC 100 240 VAC 10 AC Frequency 50...

Page 15: ...EN61000 4 5 supply 2 kV com mode 1 kV diff mode EN61000 4 6 3 V 11 How to order MODEL Y39H Instrument with mechanical keyboard a POWER SUPPLY H 100 240 VAC G 12 24 VAC VDC F 12 VAC VDC b OUT1 OUTPUT...

Page 16: ...Ascon Tecnologic Y39H Line Operating Instructions Pag 16...

Reviews: