ASCON TECNOLOGIC - Y39E
- OPERATING INSTRUCTIONS - Vr. Mondial Group - 10/10 - ISTR-MY39EENGmondial - PAG. 10
8
i.C1
Pr1 Probe Calibration
-30.0 ÷ 30.0
°C/°F
0.0
9
i.C2
Pr2 Probe Calibration
-30.0 ÷ 30.0
°C/°F
0.0
10
i.CU
Measure offset on the
display
-30.0 ÷ 30.0
°C/°F
0.0
11
i.P2
Pr2 input function:
oF = No function
EP = Evaporator
Au = Aux
dG = Digital
oF / EP / Au /
dG
EP
12
i.Fi
Function and function
logic of digital input:
0 = No function
1= Door open
2= Door open with fan
stop
3= Door open with fan
and compressor stop
4= External alarm
5= External alarm with
deactivation of control
outputs
6= Selection of active
Set Point
7= Switch on/Switch
off (Stand-by)
8= External signalling
with label “noF” and
deactivation of control
outputs
(no
alarm
output)
9= External alarm with
label
“noF”
and
deactivation of control
outputs
-9 / -8 / -7 / -6
/ -5 / -4 / -3 / -2
/ -1 / 0 / 1 / 2 /
3 / 4 / 5 / 6 / 7 /
8 / 9
0
13
i.ti
Delay
in
acquiring
digital input
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
14
i.Et
Delay to Eco mode
with door closed
oF = No function
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
oF
15
i.dS
Variable
visualized
normally on display:
oF=Display off
P1=
measurement
probe Pr1
P2=
measurement
probe Pr2
Ec = Pr1 in normal
mode, Eco in Eco
mode
SP= Active Set Point
P1 / P2 / Ec /
SP / oF
P1
r. - parameters relative to temperature control
16
r.d
Differential
(Hysteresis)
0.0 ÷ 30.0
°C/°F
2.0
17
r.Ed
Differential
(Hysteresis)
in
Eco
mode
0.0 ÷ 30.0
°C/°F
2.0
18
r.t1
Output activation time
for probe error
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
19
r.t2
Output
deactivation
time for probe error
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
20
r.HC
Output operating mode
H= Heating
C= Cooling
nr = Neutral Zone
H - C - nr
C
d. - parameters relative to defrosting control
21
d.dt
Defrosting Type:
EL=
Electrical
heating/stop. compr.
in= hot gas/reverse
cycle
EL / in
EL
22
d.di
Defrosting interval
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
6.00
23
d.Sd
Delay first defrost after
power-on
(oF = Defrost at power-
on)
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
6.00
24
d.dE
Lenght
(max.)
of
defrost cycle
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
20.0
25
d.tE
Defrost
stop
temperature
- 99.9 ÷ 999
°C/°F
8.0
26
d.Ei
Defrosting interval for
evaporator probe error
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
6.00
27
d.EE
Lengh of defrost cycle
for evaporator probe
error
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
10.0
28
d.tF
Defrost
start
temperature
- 99.9 ÷ 999
°C/°F
-99.9
29
d.St
Delay start defrost by
temperature
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
1.00
30
d.dd
Dynamic
Defrost
Percentage reduction
0 ÷ 100 %
0
31
d.cd
Delay start Defrost by
continuous
compressor
running
time
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
oF
32
d.dL
Defrost display Lock
oF= display free
on=
Lock
on
temperature
Pr1
before defrost
Lb= Lock on label
“dEF”
(during
defrosting) and “PdF”
(during
post-
defrosting)
oF - on - Lb
oF
33
d.td
Compressor
delay
after defrost (drainage
time)
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
F. parameters relative to evaporator fans control
34
F.tn
Fan
time
activation
with
ot
output
(compressor) off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
5.00
35
F.tF
Fan time deactivation
with
ot
output
(compressor) off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
36
F.FL
High temperature fan
deactivation
- 99.9 ÷ 999
°C/°F
10.0
37
F.FE
Fan
status
during
defrost
oF - on
oF
38
F.Fd
Fan delay after defrost
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
P. parameters relative to compressor protection and power