- OPERATING INSTRUCTIONS - Vr. Mondial Group - 10/10 -  ISTR-MY39EENGmondial -  PAG. 9

 

4.10.3 - OPEN DOOR ALARM

 

The  instrument  can  signal  an  open  door  alarm  by  activating  the 
digital input with the function programmed as “i.Fi” = 1, 2 or 3. 
When  the  digital  input  is  activated  the  instrument  show 

oP

  and 

after  the  delay  programmed  in  parameter 

“A.oA”,

  the  instrument 

signals  the  alarm  via  the  activation  of  the  configured  alarm  output 
(buzzer/ouput). 
At  the  intervention  of  the  open  door  alarm  the  inhibited  output  will 
reactivated  (fans or fans + compressor).

 

 

4.11 - FUNCTIONING OF KEYS “U” AND “DOWN/AUX”

 

Two  of  the  instrument  keys,  in  addition  to  their  normal  functions, 
can be configured to operate other commands. 
The  U  key  function  can  be  defined  by  the  parameter 

“t.UF”

  while 

the  DOWN/AUX  key  function  can  be  defined  by  the  parameter

 

“t.Fb” 

Both  the  parameters  have  the  same  possibilities  and  can  be 
configured for the following functions: 

=oF

 - The key carries out no function. 

=  1

  -  Pressing  the  key  for  at  least  1  second,  it  is  possible  to 

enable/disable the auxiliary output if configured (“o.Fo”=2). 

= 2

 - Pressing the key for at least 1 second, it is possible to select 

the  mode  Economic/Normal  in  rotation.  Once  selection  has  been 
made,  the  display  will  flash  the  active  set  point  code  for  about  1 
sec. (SP, Eco). 

= 3

 - Pressing the key for at least 1 second, it is possible to switch 

the  instrument  from  the  ON  status  to  Stand-by  status  and  vice 
versa. 
 

4.12 - ACCESSORIES 

The  instrument  is  equipped  with  a  connector  that  allows  the 
connection of some accessories described as follow. 

 
4.12.1 -PARAMETERS CONFIGURATION BY “A01”

 

It  is  possible  the  transfer  from  and  toward  the  instrument  of  the 
functioning  parameters  through  the  device

  A01

  with  5  poles 

connector. 
This  device  A01  it’s  mainly  useable  for  the  serial  programming  of 
the  instruments  which  need  to  have  the  same  parameters 
configuration  or  to  keep  a  copy  of  the  programming  of  an 
instrument and allow its rapid retransmission. 
The same device can connect the instrument via USB to a PC and 
through the proper configuration software tools "UniversalConf”, it’s 
possible to configure the operating parameters. 
To use the device A01 it’s necessary that the device or instrument 
are being supplied. 

SUPPLY

USB

 

SUPPLY ADAPTER

12 VDC

AC SUPPLY 

USB

 

For  additional  info,  please  have  a  look  at  the  A01  instruction 
manual. 

 
4.12.2 - “TVRY” REMOTE DISPLAY 

To the instrument it is possible to connect the remote display 

TVR 

Y

 through the special cable that can have a maximum length of 10 

m.  The device TVR Y, directly supplied by the instrument, it allows 

to visualize the temperature measured by the probe Pr1 through a 
2 ½ digit display. 

SUPPLY

TVR Y

cable 10 m MAX.

 

For  additional  info,  please  have  a  look  at  the  TVR  Y  instruction 
manual. 

 
4.12.4 -RS 485 SERIAL INTERFACE BY “TLCNV” 

The instrument can be connected by a special cable to the

 TLCNV

 

device    (mod.  C  -  TTL/RS485  interface),  by  means  of  which  it  is 
possible  to  connect  the  regulator  with  a  net  to  which  other 
instruments  (regulators  of  PLC)  are  connected,  all  depending 
typically on a personal computer used as plant supervisor.  
Using a personal computer it is possible to acquire all the function 
information  and  to  program  all  the  instrument’s  configuration 
parameters.  
The  software  protocol  adopted  for  the  instrument  is  a  MODBUS 
RTU  type,  widely  used  in  several  PLC  and  supervision  programs 
available  on  the  market  (YE  and  ZE  series  protocol  manual  is 
available on request). 
If  the  instrument  is  used  with  TLCNV  program  by  the  parameter 

"t.Ad"

 the station Address. 

Set a different number for each station, from 1 to 255. 

Note: 

The baud-rate are fixed at 9600 baud. 

TLCNV interface is directly supplied by the instrument.

 

SUPPLY

TLCNV

cable

6

5

4

8

7

9

ON

3

2

1

TX/RX

TTL

TLCNV

B

GND

A

RS 485

 

 
For  additional  info,  please  have  a  look  at  the  TLCNV  instruction 
manual.

 

 

5 - PROGRAMMABLE PARAMETERS TABLE

 

 
Here  below  is  a  description  of  all  the  parameters  available  on  the 
instrument. Some of them may not   be present because depend on 
the model/type of instrument. 
 

Par. 

Description 

Range 

Def. 

Note 

S. - parameters relative to Set Point 

1

  S.LS 

Minimum Set Point 

 

-99.9 ÷ S.HS

 

-50.0

   

2

  S.HS 

Maximum Set Point 

 

S.LS ÷ 999

 

99.9

   

3

 

SP 

Set Point

 

S.LS ÷ S.HS

 

0.0

   

4

 

SPE 

Eco Set Point

 

SP ÷ S.HS

 

0.0

   

i. -parameters relative to inputs 

5

 

i.SE 

Probes Type

 

Pt / nt

 

nt

 

 

6

 

i.Ft 

Measurement filter

 

oF ÷ 20.0 

sec

 

2.0

   

7

 

i.uP 

Unit  of  measurement 
and 

resolution 

(decimal point) 
C0 = °C with 1° res. 
F0 = °F with 1° res. 
C1 =°C with 0,1° res. 
F1 = °F with 0,1° res.

 

C0 / F0 / C1 / 

F1

 

C1

 

 

Summary of Contents for Y39E

Page 1: ...tiefk hlschr nke ALLGEMEINE GEBRAUCHSANWEISUNGEN Cod 26 23 073 Rev 6 Ihr Nordcap Fachh ndler K lte Berlin Am Pfarracker 41 12209 Berlin Fon 49 30 74 10 40 22 Fax 49 30 74 10 40 21 Mail info kaelte be...

Page 2: ...ANICAL MOUNTING 3 3 ELECTRICAL CONNECTIONS 3 4 ELECTRICAL WIRING DIAGRAM 4 FUNCTIONS 4 1 ON STAND BY FUNCTION 4 2 NORMAL MODE AND ECONOMIC MODE 4 3 MEASURING AND VISUALIZATION 4 4 DIGITAL INPUT 4 5 OU...

Page 3: ...Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROGRAMMING OF SET POINT Press the key P then release it and the di...

Page 4: ...any key for the time t Lo the instrument automatically disable the normal functions of the keys When the keyboard is lock if any of the key is pushed on the display will appear Ln to indicate the act...

Page 5: ...input configured as i Fi 1 2 or 3 If i Et oF the selection mode Eco Norm through the digital input is disabled The economic mode activated is indicated by the label Eco If i dS Ec the display in econ...

Page 6: ...o3 The outputs can be configured for the following functions ot to control the compressor or however the temperature control device dF to control the defrosting device Fn to control the fans Au to co...

Page 7: ...ble to prevent activation of the output after the instrument is turned on for the time set in the parameter P od During the power on delay phase the display shows the indication od alternating with th...

Page 8: ...s interrupted If the temperature measured by the probe is higher than the temperature set in the parameter d tE the defrosting is inhibited The active defrost is shown on the instrument display with t...

Page 9: ...but with an inverse function output activated in normal condition and disabled in alarm status L when one wants the function described as AL but with inverse logic output activated in normal conditio...

Page 10: ...eters To use the device A01 it s necessary that the device or instrument are being supplied SUPPLY USB SUPPLY ADAPTER 12 VDC AC SUPPLY USB For additional info please have a look at the A01 instruction...

Page 11: ...mode H Heating C Cooling nr Neutral Zone H C nr C d parameters relative to defrosting control 21 d dt Defrosting Type EL Electrical heating stop compr in hot gas reverse cycle EL in EL 22 d di Defros...

Page 12: ...AL t L on HE dF 52 o o3 OUT3 function see o o1 oF ot dF Fn Au At AL t L on HE Fn 53 o bu Buzzer function mode oF disable oF 1 2 3 3 1 active alarms only 2 key pressed only 3 active alarms and key pres...

Page 13: ...up to 3 relay outputs OUT1 SPST NO 16A AC1 6A AC3 1HP 250VAC 1 2HP 125 VAC OUT2 SPDT 8A AC1 3A AC3 1 2HP 250VAC 1 3HP 125 VAC OUT3 SPST NO 5A AC1 2A AC3 250 VAC 1 8HP 125 250VAC 16 A Max for common pi...

Page 14: ...2KV com mode 1 KV diff mode EN61000 4 6 3V LV 2006 95 CE EN 60730 1 EN 60730 2 7 EN 60730 2 9 Directive 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 7 5 INSTRUMENT ORDERING CODE Y39E...

Page 15: ...iegend transportiert worden sollte es erst nach 24 Stunden in Betrieb genommen werden damit das Oel wieder in den Kompressor zur ckfliessen kann Der Schrank muss ber das beiliegende Netzkabel an eine...

Page 16: ...ng flexibel F r diese Arbeit keine spitzen oder scharfe Gegenst nde benutzen welche die T rdichtung besch digen k nnten Achtung Folgende Arbeit muss von einem Servicetechniker ausgef hrt werden Schalt...

Page 17: ...schrauben IST DAS SPEISEKABEL BESCH DIGT MUSS DIESES VOM HERSTELLER BZW SEINEM KUNDENDIENST ODER AUF JEDEM FALL VON EINER QUALIFIZIERTEN PERSON ERSETZT WERDEN UM RISIKEN ZU VERMEIDEN 7 L N G E R E Z E...

Reviews: