1--5
Introduction
Device Ratings
Input Signals
Current (4):
0 to 5 A ac nominal. 4000 V ac isolation, minimum.
Burden: less than 2mV at 5 A ac input ( 0.01 VA )
Voltage (3):
0 to 600 V ac nominal, three phase. 3750 V ac isolation minimum.
Burden: less than 0.1 mA ac at 600 V ac input ( 0.1 VA ).
Frequency:
40 Hz to 100 Hz fundamental.
True RMS measurements up to and including the 21
st
harmonic.
Relay outputs (4):
Form A dry contact,
UL/CSA rated 1 A @ 30 V dc, 0.5 A @ 125 V ac resistive load
Status inputs (8):
30 V dc maximum, >10 V dc = active, <1 V dc = inactive
status input burden = 12 mA @ 24 V dc
Transfer Switch
Position input:
30 V dc maximum, >10 V dc = active, <1 V dc = inactive
Power Requirements:
24 V dc / 0.3 A maximum / 7.2 VA
Power supply should be UL Listed.
CAUTION Risk of explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to local ordinances.
Interface (s):
External display (J2) – Class 1 DB25 female type
SCI (J5) – Class 2 DB9 female type
RS485 (J1) – Isolated RS485 Communications interface
Operating Temp.:
–4
˚
F to +140
˚
F (–20
˚
C to +60
˚
C)
Storage Temp.:
–67
˚
F to +185
˚
F (–55
˚
C to +85
˚
C)
Installation Category:
IC III
Pollution Degree:
PD 2
Humidity:
Relative humidity 5% to 95%, non–condensing.
Size:
Catalog 5220T
6” H x 2 ¾” D x 10” W (152 mm H x 70 mm D x 254 mm W)
Catalog 5220D
7” H x 5” D x 12” W (178 mm H x 127 mm D x 304 mm W)
(includes Power Manager Display)
Weight:
Catalog 5220T
3 lbs. 5 oz (1.50 kg)
Catalog 5220D
5 lbs. 11 oz (2.58 kg)
(includes Power Manager Display)
Applicable Standards
UL 3111–1
Electrical Measuring and Test Equipment, Part 1: General Requirements
CAN/CSA–C22.2 No. 231–M89
CSA Safety Requirements for Electrical and Electronic
Measuring and Test Equipment