3--14 Initial Set up
Setpoint Configuration
Twelve user–configurable setpoints are available. The operator can select
any combination of parameters from the following list:
S
KW overload prealarm
S
reverse power
S
KW overload alarm
S
reverse VARS
S
over voltage
S
reverse over current
S
under voltage
S
negative sequence over current
S
over frequency
S
negative sequence voltage
S
under frequency
Additionally, the 8 digital inputs and switch–position input can be used as
setpoints. Each setpoint allows the user to select:
S
the parameter
S
the trip time delay
S
the trip level
S
the reset time delay
S
the reset level
S
the digital output
The user can select any combination of the four available digital outputs and
choose whether an acknowledgment is required to reset a tripped setpoint.
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< SETTINGS >>>
Setpoints
Press left & right
arrow keys until
Setpoints setup
location appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<<< Setpoint 1A >>>
Param:
none
Trip:
0 %
Reset:
0 %
First setpoint
screen ’A’.
6
<<< Setpoint 1B >>>
TD Operate:
10.0 sec
TD Release
10.0 sec
Output(s)
NONE
Press right arrow
key. Second set-
point screen ’B’.
7
<<< Setpoint 1B >>>
TD Operate:
10.0 sec
TD Release
10.0 sec
Output(s)
NONE
Saves the set-
tings. Nothing is
blinking.
Now press the
Esc
key to return to the top level display.