![Asco Power Manager Xp 5200 Series Operator'S Manual Download Page 36](http://html.mh-extra.com/html/asco/power-manager-xp-5200-series/power-manager-xp-5200-series_operators-manual_2981113036.webp)
3--19
Initial Set up
Event Log
The
Power Manager Xp
contains an event log which records up to 100 events
as configured by the setpoints. The events are numbered 0 – 99 with event
0 being the most recent event. When more then 100 events occur, the oldest
events are removed to record the newer events.
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< Event
Log >>>
Event # 0
08:18:56
TUE SEP / 12 /00
KW DEMAND
TRIP’D
Press left & right
arrow keys until
Event Log
appears.
4
<<< Event
Log >>>
Event # 0
08:18:56
TUE SEP / 12 /00
KW DEMAND
TRIP’D
Press up & down
arrow keys to
scroll through all
recorded events.
Now press the
Esc
key to return to the top level display.