3--13
Initial Set up
Watt Demand Window Size
The integration time period for the watt demand calculation is user
selectable from one to fifteen minutes in one minute increments. It is
recommended that the user selects this option to be one–third of the billing
interval. Set this option as follows:
Step
Press
Display Shows
Comment
1
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA ATS
o
n NORM
Brings you to
top level if not
already there.
2
<<< SETTINGS >>>
System: 3
f
–4W WYE
Source: LOAD
KW Capacity:
0 KW
3
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output: NOT USED
Press left & right
arrow keys until
the
Clear Max
Demand
location
appears.
4
<<< SETTINGS >>>
Enter password
0000
Enter password
as explained in
steps 5 & 6 on
page 3–1.
5
<<< SETTINGS >>>
Clear Max Demand?
NO
Window Size:
15 min.
SP–Output:
NOT USED
The word NO
is blinking.
6
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15
min.
SP–Output:
NOT USED
Window Size
is blinking.
7
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15
min.
SP–Output:
NOT USED
Press up & down
arrow keys until
correct number
is displayed.
8
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output:
NOT USED
SP–Output
is blinking.
9
<<< SETTINGS >>>
Clear Max Demand? NO
Window Size:
15 min.
SP–Output:
NOT USED
Saves the new
setting. Nothing
is blinking.
Now press the
Esc
key to return to the top level display.