IRD1560 Decoder User Manual
Item
Requirement
Machine Hall Space
When user installs machine frame array in one machine hall, the distance
between 2 rows of machine frames should be 1.2 ~ 1.5 m and the
distance against wall should be no less than 0.8 m.
Machine Hall Floor
Electric isolation, dust free
Volume resistivity of ground anti-static material: 1×10
7
~ 1×10
10
Ω
,
Grounding current limiting resistance: 1M (Floor bearing should be
greater than 450 kg/m
2
)
Environment Temperature
5~40
°C
(sustainable), 0~45
°C
(short time),
installing air-conditioning is recommended
Relative Humidity
20% ~ 80% sustainable 10% ~ 90% short time
Pressure
86 ~ 105 kPa
Door & Window
Installing rubber strip for sealing door-gaps and dual level glasses for
window
Wall
It can be covered with wallpaper, or brightness less paint.
Fire Protection
Fire alarm system and extinguisher
Power
Requiring device power, air-conditioning power and lighting power are
independent to each other. Device power requires AC power 100 ~ 240V
50 ~ 60Hz. Please carefully check before running.
All function modules’ good grounding is the basis of reliability and stability of devices. Also,
they are the most important guarantee of lightning arresting and interference rejection.
Therefore, the system must follow this rule.
Coaxial cables outer conductor and isolation layer should keep proper electric conducting with
the metal housing of device.
Grounding conductor must adopt copper conductor in order to reduce high frequency
impedance, and the grounding wire must be as thick and short as possible.
Users should make sure the 2 ends of grounding wire well electric conducted and be antirust.
It is prohibited to use any other device as part of grounding electric circuit
The area of the conduction between grounding wire and device’s frame should be no less than
25mm
2
.
All the machine frames should be connected with protective copper strip. The grounding wire
should be as short as possible and avoid circling. The area of the conduction between
grounding wire and grounding strip should be no less than 25mm
2
.