Up to 32 single load devices can be connected to one RS-485 system without using a repeater. As this 
module is a 1/8 load device, up to 256 modules can be connected to the bus. Repeaters can be used to 
extend the maximum transmission distance and increase device count if needed. 

x

 

A screened, twisted-pair cable should be used. The cable screen should be connected to the COM 
terminal and connected to safety ground at one point. 

 
NOTE

: In some cases, better performance is achieved if no COM connection is made. Device can operate with 2 

wire connection. 
 

x

 

The pump contains neither termination nor bias circuitry. RS-485 wiring should be externally terminated 
if needed. For short wiring and/or low baud rate, interface can operate without termination. However, 
it is recommended that termination (100-150 ohm resistor) is added on both ends of bus wiring. There 
are wiring length limits regarding to speed and termination: 

 

 

NOTE: 

Any branch/derivative cable is considered unterminated. Keep them short, below 250m combined for 

maximum speed and reliability. 

5.6.4  SERIAL COMMUNICATION DEFAULT SETTING (SPEED, PARITY AND ADDRESS) 

 

MODBUS RTU:

 By default, each device is set to 19200-E-1 (even parity), address 245. Setup the registers to 

configure each device before connecting it to existing network. Othwerise you can power each device one by 
one, configuring the settings before adding another one. 
 

BACNET MST/TP:

 By default, each device is set to 38400 baud, MAC 1. Use web interface to modify configuration. 

 
 

5.8

 

BMS COMMUNICATION OVER MODBUS  

5.7.1  MODBUS RTU OVER RS-485

 

 
AGE4 pump is a Modbus RTU slave. Typically, only one master device is connected to the serial bus, and one or 
several slaves are also connected to the bus.  

 

5.7.2 MODBUS OVER ETHERNET

 

 
Modbus device is available at port 502. Default address is thus 192.168.0.245:502. Supported protocols are 
Modbus TCP, Modbus RTU over TCP, Modbus UDP and Modbus RTU over UDP. The protocol is automatically 
recognized according to received packet and no additional configuration is needed. 

NOTE: 

Device ID equals slave address. Controller requests must match this value [245 by default]. 

 

 

 

Summary of Contents for AGE4

Page 1: ...AGE4 variable speed circulator AGE4 D high power Installation and operating instructions File No 10 8506iec Date july 18 2022 Supersedes new Date new...

Page 2: ...2...

Page 3: ...U Standard used EN 60335 1 EN 60335 2 51 x Electromagnetic compatibility 2014 30 EU Standard used EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 x Ecodesign Directive 2009 125 EC Standard used EN 162...

Page 4: ...lectrical specification 7 4 Pump installation 10 4 1 Mechanical Installation into system pipework 10 4 2 Hydraulic Installation into system 11 4 3 Electrical installation 12 4 4 BMS COMMUNICATION and...

Page 5: ...AGE4 D 40 120 AGE4 Pump family D Twin pump 40 Nominal pipe diameter 120 MAX head in 0 1 m of H2O 1 3 PUMP MAINTENANCE SPARE PARTS AND DECOMMISSIONING Pumps are designed to operate without maintenance...

Page 6: ...mp should not be used for pumping flammable corrosive media and in an corrosive atmosphere Permanent magnet rotor inside the pump is prone to accumulating magnetic particles on its surface which can l...

Page 7: ...ctions see chapter 5 Setup and operation Detailed specifications about used protocols are described in communications manual 3 4 2 1 DIGITAL INPUT RUN 0V Available on all AGE4 models Electrical proper...

Page 8: ...pe Screwless terminals 2 1 pins See section 3 1 Terminals Data protocol Modbus RTU BACnet MS TP Only one at a time Selectable over Web interface tab Network Bus wire configuration Two wire common Cond...

Page 9: ...t 38400 Modbus over Ethernet Server address 192 168 0 245 502 IP address is the same as for pump web server port is fixed as 502 Device address 245 Default value can be changed over Modbus Data format...

Page 10: ...the pump For the pump to operate with minimal vibrations and noise it should be installed into the pipework with its axis or shaft in horizontal position as showed in figure 1 The small rectangular op...

Page 11: ...nd the outlet side of the pump Ambient environment around the pump should be dry and illuminated as appropriate and the pump should not be in direct contact with any objects Pump seals prevents dust a...

Page 12: ...temperatures that could cause injury x Motor housing should not be termally insulated 4 3 ELECTRICAL INSTALLATION Electrical connection is done with connector supplied with the pump pumps with power 2...

Page 13: ...RTU Pump has built in MODBUS RTU connection through which the pump can be controlled and feedback data can be read using the RS 485 standard Modbus RTU allows us to set and view x Regulation mode sett...

Page 14: ...mon return SET2 MAX Control signal 2 SET3 FB Control signal 3 24V 24 V 50 mA output only on some models NC Normally closed relay contact Opens when relay is active C Relay common contact NO OK Normall...

Page 15: ...x Digital input RUN to put pump in RUN STANDBY state x Relay outputs to signalizes pumps status and pumps fault condition x 10 step switch it allows to change relays command analog inputs outputs sett...

Page 16: ...m speed Hi 3 Stop 7 Reference point 8 Reference point 9 Reference point CONTROL VARIABLES Pump will respond to external controls according to selected pump operating mode Consult proper pump operating...

Page 17: ...when not changing parameter values x Scrolling through modes downwards when mode selection is selected x Changing parameters downwards when setting parameter values Long press x seconds together with...

Page 18: ...PUMP MODES AND PARAMETERS For transition between modes we hold the key for 3 seconds and then select the mode in which we wish the pump to operate with or keys We confirm the selection with the key A...

Page 19: ...ve and to min settings when SET1 is inactive SET3 FB Default Mode 1 10 V voltage output used for activating SET 1 and SET2 by connecting them to SET3 Configuration Function description Fault The relay...

Page 20: ...n also be used RS 485 Modbus interface 3 5 Reserved Reserved for future or customer specific use 6 Show relay configuration LED1 and LED2 will show relay configuration 7 Change relay configuration Rel...

Page 21: ...twin pump 3 Turning the pump on and off again 4 Setting the 10 step switch to number 1 5 Turning the pump on 5 3 MODE 1 2 10V Mode 1 is most often used mode of operation It has 2 pre prepared inputs...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24 5 4 MODE 2 0 10V...

Page 25: ...25 5 5 RELAYS OUTPUT...

Page 26: ...he pump maintains the currently set pressure Hset on the drawing from 0 flow to MAX IIimum power where the pressure begins to drop At constant pressure we can only set the pressure Hset on the drawing...

Page 27: ...ne on standby will automaticaly start working This mode can be set up by turning off the pump that we wish to be on standby x Parallel operation Both pumps work at the same time with the same settings...

Page 28: ...considered unterminated Keep them short below 250m combined for maximum speed and reliability 5 6 4 SERIAL COMMUNICATION DEFAULT SETTING SPEED PARITY AND ADDRESS MODBUS RTU By default each device is s...

Page 29: ...ll addresses contain 16 bit one Word registers Some are bit interpreted while others are combined for a 32 bit value NOTE All register addresses are 1 based Address 001 is thus transmitted over bus as...

Page 30: ...30...

Page 31: ...on Description 021 022 RESERVED 023 SoftwareVersion BMS Module software version 024 029 RESERVED 030 ProductVersion Product version 32x for BMS module x denotes hardware revision 031 RESERVED 032 Soft...

Page 32: ...32 5 7 7 PUMP STATUS REGISTERS Registers in this block can be read by means of function codes 0x03 and or 0x04 They are read only...

Page 33: ...33 5 7 8 PUMP DATA REGISTERS Registers in this block can be read by means of function codes 0x03 and or 0x04 They are read only...

Page 34: ...umps enables BACnet MS TP communication with compatible pumps BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Advanced Operator Workstation B AWS BACnet Operator Di...

Page 35: ...on with MS TP slaves and certain other devices Yes No NETWORKING OPTIONS None SECURITY OPTIONS Non secure Device is capable of operating without BACnet Network Security CHARACTER SETS SUPPORTED ISO 10...

Page 36: ...36 5 8 2 ANALOG INPUTS OBJECT TYPE 0 NOTE Values are read only 5 8 3 ANALOG OUTPUTS OBJECT TYPE 1...

Page 37: ...37 5 8 3 BINARY INPUTS OBJECT TYPE 3 NOTE Values are read only 5 8 3 BINARY OUTPUTS OBJECT TYPE 4...

Page 38: ...on circuit current cannot be controlled E3x Pump errors E31 Software motor protection active Average motor current was too high pump load is much higher than expected E4x Device specific error codes E...

Page 39: ...39...

Page 40: ...shanghai china 200085 86 21 5237 0909 s o paulo rua jos semi o rodrigues agostinho 1370 galp o 6 embu das artes sao paulo brazil 55 11 4785 1330 beijing room 1612 nanyin building no 2 north east thrid...

Reviews: