5.2.2 RELAYS OUTPUTS
Active relay position
Deactivated relay position
5.2.3 DIGITAL INPUT (START/RUN)
Inputs RUN/0V
Function description
Connected
Pump runs.
Disconeected
Pump in standby state.
5.2.4 ANALOG INPUT/OUTPUT (SET1, SET2, SET3)
Input/Output
Function
Function description
SET1
Run
[Default - Mode 1]
Turning the pump on/off. By default activating with
connection to SET3.
SET2
MAX/Min
[Default - Mode 1]
Set the pump to MAX settings when SET1 is active and to
min. settings when SET1 is inactive.
SET3
FB
[Default - Mode 1]
10 V voltage output used for activating SET 1 and SET2 by
connecting them to SET3.
Configuration
Function description
Fault
The relay is in active position only when the pump is powered up and an error is
present.
Ready
[Default]
The relay is in active position when the pump is powered up and no error is
present. If an error occurs, relay will deactivate.
Run
The relay is in active position when the pump is powered up and running. If the
pump is stopped or an error occurs, relay will deactivate.
No function
Relay is always in deactivated position.
Always on
Relay in active position