5.2.6 RESETTING PUMP TO FACTORY SETTINGS
For resetting the pump to factory default settings all three buttons (
,
,
) must be held for 5 seconds. The
pump will reset to automatic mode, delete previous duty head settings and power settings and unlock setting
pump operation (if previously locked).
For resetting of pump communications and BMS I/O, follow the steps below:
1.
Disconnecting power from pump,
2.
Set the 10-step switch to number 9
4
(or 8 for left twin pump),
3.
Turning the pump on and off again,
4.
Setting the 10-step switch to number 1,
5.
Turning the pump on.
5.3
MODE 1 (2..10V)
Mode 1 is most often used mode of operation. It has 2 pre-prepared inputs that can be used for either digital
control or with analog control voltages. Additional 10.5V output provides voltage feedback for analog or digital
control.
SET1 / RUN
RUN input Signal load 0.5 mA.
COM / 0V
Common ground for voltage input.
SET2 / MAX
MAX input. Signal load 0.5 mA
SET3 / FB10.5 V feedback voltage for SET1 and SET2.
DIGITAL (SWITCH) CONTROL
4
This also sets up the right twin pump.
Terminals
Signal function
Mode 1 connection for Switch mode