14
4.5
CONTROLS WIRING (I/0, SERIAL COMMUNICATION)
MODE
Mode selection rotary switch. Position read at power-on. Used to configure mode of
operation for the circuit. See section 4.3 “Modulemode selection”.
LED1 / LINK
Slowly blinking when module is powered.
Blinking fast on Modbus Error
Permanently lid when Ethernet link established.
Ethernet
10BASE-T RJ-45 connector.
LED2 / ACT
Indicates Ethernet activity or RS-485 activity.
B/D-
RS-485 negative data signal.
A/D+
RS-485 positive data signal.
SET1 / RUN
Control signal 1.
COM / 0V
RS-485 common and analog input common return.
SET2 / MAX
Control signal 2.
SET3 / FB
Control signal 3.
+24V
24 V, 50 mA output (only on some models)
NC
Normally closed relay contact. Opens when relay is active. C
Relay common contact.
NO / OK
Normally open relay contact. Closes when relay is active.
For all AGE4 with motor rated power > 200W
NOTE:
To maintain pump IP (ingress protection), the network cable should be pulled through the gland inlet
and then crimped to a connector.
4.6
WIRING CONSIDERATIONS
x
All cables connected must be heat-resistant to at least +85 °C.
x
All cables connected must be installed in accordance with EN 60204-1.
x
All wires to the communications module must be connected to the terminals or cut. No loose wiring
permitted.
Terminal
Terminal layout with factory configuration