20
5.2.5 10-STEP
SWITCH
There is a mode selection rotary switch in the terminal box. It can be rotated by gently inserting a screwdriver
into the arrow mark on top and rotating the switch to desired value.
Switch setting is used when the pump turns on! More details about different modes can be found in
communications manual.
Mode
switch
position
Function
Description
0
Free configuration
Terminal functions are configured over Ethernet interface.
1
Mode 1
(2-10V control)
SET1 = RUN input
SET2 = MAX speed input
SET3 = FB (10.5 V) output, used to supply RUN and MAX inputs. External
voltage source can also be used.
RS-485 = Modbus interface.
2
Mode 2
(0-10V control)
SET1 = RUN input
SET2 = SPEED input
SET3 = FB (10.5 V) output, used to supply RUN and MAX inputs. External
5-24 V voltage source can also be used.
RS-485 = Modbus interface
3..5
Reserved
Reserved for future or customer specific use.
6
Show relay
configuration
LED1 and LED2 will show relay configuration.
7
Change relay
configuration
Relay configuration will be increased (0->1, 1->2, 2->0) when electricity
is turned on.
LED1 and LED2 will show current relay configuration.
8
Twin reset to factory
Same as Mode 9, with exception of:
module IP address is set to 192.168.0.246
Twin IP address is set to 192.168.0.245
9
Reset to factory
This mode will set communication interface to default values. Main
purpose is to restore default settings.
NOTE:
x
Disconnect any SET1, SET2 and SET3 connections when using
this mode to prevent possible harm to controller. SET1, SET2,
SET3 will output test voltages of 10 V, 7 V and 5 V respectively.
RS-485 port is actively driven. Relay will cycle. This is used for
testing purposes.
x
It is recommended that all module wires are disconnected to
prevent possible harm to external controllers.