5
2014-03-03 / 06
TECHNICAL DATA
BioCompPX
Max. output pellets
kW
18-60
Water volume boiler
litres
175
Max. operating pressure
bar
3.0
Max. operating temperature
C
130
Efficiency
%
>90
Weight (gross)
kg
495
Rec. chimney diameter
mm
150
Rec. chimney height
m
5
Height
mm
895
Diameter
mm
430
Volume
m
3
0.13
Electrical connection
Permanent connection via an isolator switch
220-240 Vac 50Hz,350W
Load on heating surface
kW/m
2
11.1
Size of burner opening
mm x mm
250x250
Size of flue
Ø
mm
139
Required underpressure
Pa
> 5
Smoke Gas Temperature nominal effect 60 kW
°C
ca 140
Smoke Gas Temperature min effect 18 kW
°C
ca 85
Pressure drop acrossthe boilerwater connections
26 mbar @ 2,5m
3
/h
107 mbar vid 5,2 m
3
/h
Supply/return connection
DN
50
Connection for expansion
DN
25
Thermostat connection
DN
15
Flat heat exchanger, output
kW
57
Heat exchanger pump
UPS 25-40
Noise level
dbA
62
Class according to 303-5 2012
class
5