/ 89
MENU
SUB-MENU
PARAMETER DESCRIPTION
RANGE
FACTORY SETTINGS
19
1
0
Connectivity Status
OFF
Initialization
Idle
Acess Point initializing
Acess Point mode on
Station Mode - Connecting
Station Mode - Connected
Station Mode - Provisioning
Station Mode - Server Connected
Wifi error
19
1
1
Signal Level
19
1
2
Active Status
Not provisioned
Provisioned - Not active
Active
19
1
3
Serial Number
19
1
4
SW Upgrade Status
Initialization
Waiting for Update
Updating Micro 1
Updating Micro 2
19
1
5
On line outdoor temperature
OFF – ON
OFF
19
1
6
On line weather data
OFF – ON
OFF
19
2
Reset Menu
19
2
0
Re-confi guration
Resettare? OK=Yes, esc=No
20
Buff er
20
0
Confi guration
20
0
0
Buff er Activation
OFF - ON
OFF
20
0
1
Buff er charge mode
Partial charge (1 sensor)
Full charge (2 sensors)
Partial charge (1 sen-
sor)
20
0
2
Buff er setpoint temp. hysteresis
0 ÷ 20°C
5°C
20
0
3
Buff er setpoint temperature heating
[20 ÷ 70°C]
40°C
20
0
4
Buff er setpoint temperature cooling
[5 ÷ 23°C]
18°C
20
0
5
SG Ready Buff er setpoint
[20 ÷ 70°C]
40°C
20
0
6
Off set of PV Integration Setpoint
[0 ÷ 20°C]
0°C
20
0
7
Buff er Setpoint mode
Fixed
AUTO function
Fixed
20
1
Diagnostics
20
1
0
Buff er temperature sensor (Low)
only reading
20
1
1
Buff er temperature sensor (Mid) (not used)
only reading
20
1
2
Buff er temperature sensor (High)
only reading
20
1
3
Buff er charge request
OFF – ON
only reading
20
2
Statistics
20
2
0
Buff er charge hours Heating (/10)
only reading
20
2
1
Buff er charge hours Cooling (/10)
only reading