/ 85
MENU
SUB-MENU
PARAMETER DESCRIPTION
RANGE
FACTORY SETTINGS
12
2
3
Text for HP disabling
- 20°C - Text for Boiler disabling
-20°C
12
2
4
External temperature correction
-3°C - +3°C
0°C
12
2
5
Pro-Tech anode active
OFF - ON
OFF
12
2
6
EM Antiblocking Function Enable
OFF - ON
OFF
12
3
Central Heating
12
3
0
CH pump prerun time
30 - 255 sec.
30 sec.
12
3
1
Time for prerun new attempt
0 - 100 sec.
90 sec.
12
3
2
CH Pump Overrun
0 - 15 min. ; 16 = always active
3 min.
12
3
3
Pump Speed Control
Low Speed
High Speed
Modulating
Modulating
12
3
4
Delta T Pump Setpoint
5°C - 20°C
5°C
12
3
7
Max PWM Pump
Min PWM pump - 100%
100%
12
3
8
Min PWM Pump
20% - Max PWM pump
40%
12
3
9
Floor drying Flow Set Point T
25°C - 60°C
55°C
12
4
Cooling
12
4
0
Cooling mode activation
Not active
Active
Not active
12
4
1
Cooling anticycling time
0 - 10 min
3 min.
12
4
2
Cooling FlowT HP Off set
0°C , -10°C
-2°C
12
5
Domestic Hot Water
12
5
0
DHW Comfort Setpoint T
35°C - 65°C
55°C
12
5
1
DHW Reduced Set Point T
35°C - DHW Comfort Tenperature
35°C
12
5
2
Comfort Function
Disabled
Time based
Always Active
Always Active
12
5
3
Tank charge mode
Standard
Only HP
Fast
Standard
12
5
4
Thermal Cleance Function
OFF - ON
ON
12
5
5
Thermal Cleance start time [hh:mm]
[00:00-24:00]
01:00
12
5
6
Thermal Cleance frequency
1 ÷ 30 days
30 days
12
5
7
DHW delay timer
10 ÷ 120 min
30 min
12
5
8
Soglia DHW Release Integral
15 ÷ 200 °C*min
60°C*min
12
6
Manual Mode - 1
9
6
0
Manual mode activation
OFF - ON
OFF
12
6
1
HP circulator control
OFF
Low Speed
High Speed
OFF
12
6
2
Diverter valve control
DHW
CH
DHW
12
6
3
Diverter valve COOLING
CH
COOLING
CH
12
6
4
Auxiliary circulator
OFF - ON
OFF
12
6
5
Output AUX 1/2 contact
OFF - ON
OFF
12
6
6
Force Hp Heat
OFF - ON
OFF