Operation Guide
P341/EN O/B11
Commissioning and
CHAPTER 3
Maintenance
Page 13/80
MiCOM P341
Supply Rail
Terminals
+ve
F7 & F8
–ve
F9 & F10
Table 4:
Field voltage terminals
4.2.5
Input opto-isolators
This test checks that all the opto-isolated inputs are functioning correctly. The P341
relays have 8 opto-isolated inputs.
The opto-isolated inputs should be energised one at a time. Ensuring correct polarity,
connect the field supply voltage to the appropriate terminals for the input being
tested. The opto-isolated input terminal allocations are given in Table 5.
Note: The opto-isolated inputs may be energised from an external dc auxiliary
supply (e.g. the station battery) in some installations. Check that this is not
the case before connecting the field voltage otherwise damage to the relay
may result. If an external 50Vdc supply is being used it will be connected to
the relay’s optically isolated inputs directly. However, if the auxiliary supply
rating is either 110 – 125Vdc or 220 – 250Vdc, it will be connected to the
optically isolated inputs via an external resistor box (our product number
GJ0229 006 or 007). If an external supply is being used then it must be
energised for this test but only if it has been confirmed that it is suitably rated
with less than 12% ac ripple.
The status of each opto-isolated input can be viewed using either cell
[0020: SYSTEM DATA, Opto I/P Status] or [0F01: COMMISSION TESTS, Opto
I/P Status], a ‘1’ indicating an energised input and a ‘0’ indicating a de-energised
input. When each opto-isolated input is energised one of the characters on the
bottom line of the display will change to the value shown in Table 5 to indicate the
new state of the inputs.
Apply Field Voltage
to Terminals
Input
-ve
+ve
Cell [Opto I/P Status] Value
Opto input 1
D1
D2
0000000000000001
Opto input 2
D3
D4
0000000000000010
Opto input 3
D5
D6
0000000000000100
Opto input 4
D7
D8
0000000000001000
Opto input 5
D9
D10
0000000000010000
Opto input 6
D11
D12
0000000000100000
Opto input 7
D13
D14
0000000001000000
Opto input 8
D15
D16
0000000010000000
Table 5:
Opto-isolated input terminals
Summary of Contents for MiCOM P341
Page 1: ...MiCOM P341 Interconnection Protection Relay Operation Guide P341 EN O B11...
Page 2: ......
Page 3: ...Operation Guide MiCOM P341 Interconnection Protection Relay Volume 2...
Page 4: ......
Page 6: ...P341 EN O A11 Operation Guide Issue Control MiCOM P341...
Page 8: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 10: ......
Page 12: ......
Page 17: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 1 Introduction...
Page 18: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 41: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 2 Installation...
Page 42: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 44: ...P341 EN O B11 Operation Guide CHAPTER 2 Installation Page 2 10 MiCOM P341...
Page 53: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 3 Commissioning and Maintenance...
Page 54: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 58: ...P341 EN O B11 Operation Guide CHAPTER 3 Commissioning and Page 4 80 Maintenance MiCOM P341...
Page 135: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 4 Problem Analysis...
Page 136: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 138: ...P341 EN O B11 Operation Guide CHAPTER 4 Problem Analysis Page 2 8 MiCOM P341...
Page 145: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX A Relay Menu Database...
Page 273: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX B External Connection Diagrams...
Page 274: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 278: ...P341 EN O A11 Operation Guide MiCOM P341...
Page 281: ......