P341/EN O/B11
Operation Guide
CHAPTER 2
Installation
Page 6/10
MiCOM P341
Figure 2:
Rack mounting of relays
Relays can be mechanically grouped into single tier (4U) or multi-tier arrangements
by means of the rack frame. This enables schemes using products from the MiCOM
and MiDOS product ranges to be pre-wired together prior to mounting.
Where the case size summation is less than 80TE on any tier, or space is to be left for
installation of future relays, blanking plates may be used. These plates can also be
used to mount ancillary components. Table 1 shows the sizes that can be ordered.
Note:
Blanking plates are only available in black.
Further details on mounting MiDOS relays can be found in publication R7012,
“MiDOS Parts Catalogue and Assembly Instructions”.
Case Size Summation
Blanking Plate Part Number
5TE
GJ2028 001
10TE
GJ2028 002
15TE
GJ2028 003
20TE
GJ2028 004
25TE
GJ2028 005
30TE
GJ2028 006
35TE
GJ2028 007
40TE
GJ2028 008
Table 1:
Blanking plates
Where an external dc supply (e.g. station battery) greater than 54V is being used to
energise the optically isolated inputs of a relay, resistor boxes mounted external to the
relay are available to reduce the voltage across the inputs. Table 2 details the two
versions of external resistor box that are available.
Note:
Each box contains 8 resistors. Therefore one external resistor
box is required for each input board in the relay being used (i.e.
one external resistor box for each 8 optically isolated inputs).
Summary of Contents for MiCOM P341
Page 1: ...MiCOM P341 Interconnection Protection Relay Operation Guide P341 EN O B11...
Page 2: ......
Page 3: ...Operation Guide MiCOM P341 Interconnection Protection Relay Volume 2...
Page 4: ......
Page 6: ...P341 EN O A11 Operation Guide Issue Control MiCOM P341...
Page 8: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 10: ......
Page 12: ......
Page 17: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 1 Introduction...
Page 18: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 41: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 2 Installation...
Page 42: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 44: ...P341 EN O B11 Operation Guide CHAPTER 2 Installation Page 2 10 MiCOM P341...
Page 53: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 3 Commissioning and Maintenance...
Page 54: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 58: ...P341 EN O B11 Operation Guide CHAPTER 3 Commissioning and Page 4 80 Maintenance MiCOM P341...
Page 135: ...Operation Guide P341 EN O B11 MiCOM P341 CHAPTER 4 Problem Analysis...
Page 136: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 138: ...P341 EN O B11 Operation Guide CHAPTER 4 Problem Analysis Page 2 8 MiCOM P341...
Page 145: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX A Relay Menu Database...
Page 273: ...Operation Guide P341 EN O B11 MiCOM P341 APPENDIX B External Connection Diagrams...
Page 274: ...P341 EN O B11 Operation Guide MiCOM P341...
Page 278: ...P341 EN O A11 Operation Guide MiCOM P341...
Page 281: ......