Reading of the instrument internal features
Access to the submenu reading of the internal features
Type of the instrument: DIP400, DIP 401, DIP 402
Identification numbers
Programme version
Programme version number
Option code
Value of the option code
Self-diagnosis error
Error type
Display of the check sum
Value of the check sum
About
d40x
n0
A0007
ProG
08.00
OPt
Ar---.
Err.
0000
CSUM
FC4E
Saving of the configuration
Saving of the configuration
Saving No saving
Other functions
Display of the minimum value
Display of the maximum value
Deleting of the min. and max.
Error messages
Value set out of range
Sensor rupture
Blinking measure: measure in overrange
Displayable value overload
Upper or lower electrical overstepping of the input
Self-diagnosis error
«
Return value (or not) of the output in case of
self-diagnosis error
Return value required
No return value
Return value
out.I
out.U
or
no
YES
rEPLi
9. ANNEXE: MODBUS
Word address
0
1
2
3
4
5
6
7
8
9
12
13
14
15
Description
Sensor primary measure
decimal point / unit
final measure
decimal point / unit
final measure min.
decimal point / unit
final measure max.
decimal point / unit
value of the analog output n°1
decimal point / unit
Auto diag 1
Auto diag 2
Status of the relay 1
Status of the relay 2
9.1 Table of the modbus addresses
Measures
The following parameters: sensor primary measure, final measure, min.
and max. of the final measure and the values of the analog outputs are
transmitted in the form of a module and a unit associated with a position
of the decimal point.
Eg.:
Word address
0
1
Decimal value
10 094
12 289
Encoding
module
dec. point / unit
Encoding of the integer decimal point/ unit
H
L
dec. point
unit: code of correspondance in the list hereunder
0: no decimal
0: none
16: 1 decimal
1: V
32: 2 decimals
2: kV
48: 3 decimals
etc ...
Eg.: 12 289 = 48 X 256 + 1
The integer encodes the unit V with 3 decimals.
The measure read is thus 10.094 V.
BYTE
BYTE
E.xxx
}