p11
Out.P
Exit from the programming with or without saving
exit and
save the
configuration
exit without
saving the
configuration
revert to the
measure display
Note: An exit from the programming mode with saving of the configuration
(
SAVE, YES
) will automatically reset the tare, the min. and the max. as well as the
alarm recordings to 0.
4.5.1 Current input
•
Linear
:
Features
Measurable limits of the input: -22 to 22 mA
4.5 Features of the inputs and programming limits
MA
«
Caliber
Display
resolution
Accuracy
from -20 to
+20mA
± 1 digit
0.1% of the MR
4.5.2 Voltage input
• Linear
: Features
U
«
Caliber
Display
resolution
Accuracy
-100 to +100 mV
-1 to + 1 V
-10 to +10 V
-300 to 300 V
± 1 digit
0.1% of the MR
Measurable limits: -10% to +10%
That is for example for the caliber 1V: -1.1V to +1.1V
Sensor type
Measurable limits of the input
Accuracy
(MR: measure range)
Pt 100
-200 / 850 °C
-328 / 1562 °F
*
± 0.1% of the MR
*
The influence of the line resistance with 0<Rl<25
Ω
is included in the
accuracy class.
ni 100
-60 / 260 °C
-76 / 500 °F
± 0.1% of the MR
Delta Pt 100
-200 / 270 °C
-328 / 518 °F
± 0.1% of the MR
• Unlinear:
(see
page 17
)
4.5.3 Temperature input
•
Resistive sensor
Platinium sensor Pt 100
Ω
in 3-wire mounting
Measurement of Delta Pt100 2 wire
ni 100
Ω
nickel sensor
•
Thermocouple
Type: J, K, N, S, B, W5, T, R, E, W, W3, L
Efficiency of the cold junction compensation:
0.03°C / °C ±0.5°C from -5°C to +55°C
Cold junction compensation
Internal
External Programmable from -10°C to 60°C
+14°F to 140°F
Pt 100
ni 100
dPt
Pt 100
«
dPt
«
ni 100
«
CJC-I
CJC
CJC-E
SAvE
no
YES
Out.P
tc
tc