ALARMS

ALARM RELAY MANAGEMENT

DIGITAL INPUT

ALC Temperature alarms configuration:

 (Ab; rE)

Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = temperature 
alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the 
“SET+ALU” or “SET-ALL” values.

ALU MAXIMUM temperature alarm:

 (SET÷150°C; SET÷302°F) when this temperature is reached the 

alarm is enabled, after the “ALd” delay time.

ALL Minimum temperature alarm:

 (-100.0 ÷ SET°C; -148÷302°F) when this temperature is reached the 

alarm is enabled, after the “ALd” delay time.

AFH Differential for temperature alarm recovery:

 (0,1÷25,5°C; 1÷45°F) Intervention differential for 

recovery of temperature alarm.

Ald Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and 

alarm signalling.

dAo Exclusion of temperature alarm at startup:

 (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling.

tbA Alarm relay silencing (with oA1=ALr):

 (n= silencing disabled: alarm relay stays on till alarm 

condition lasts, y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm).

Aro Alarm relay activation with power failure:

y = the alarm relay is activated if a temperature alarm happens during a power failure
n = the alarm relay is never activated during a power failure

ALF Alarm relay activation for all the alarms:

y = the alarm relay is activated for all the alarms
n = the alarm relay is activated only in case temperature alarms and regulation probe failure.

bon Time of buzzer restart after muting, in case of alarm duration:

 (0÷30min; with 0 the buzzer is 

always off after muting)

AoP Alarm relay polarity:

 it set if the alarm relay is open or closed when an alarm happens.

CL= terminals 1-2 closed during an alarm; oP = terminals 1-2 open during an alarm

i1P Digital input polarity:

 oP: the digital input is activated by opening the contact; CL: the digital input is 

activated by closing the contact.

i1F

Digital input configuration:

 EAL = external alarm: “EA” message is displayed; bAL = serious alarm 

“CA” message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor = door 
switch function; dEF = activation of a defrost cycle; AUS =to switch on the second relay if oA1 = AUS; 
Htr = kind of action inversion (cooling – heating); FAn = not set it; ES = Energy saving.

did:

(0÷255 min) 

with i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the detection of 

the external alarm condition and its signalling. 

with i1F= dor: door open signalling delay

 

with i1F = PAL: time for pressure switch function:

 time interval to calculate the number of the 

pressure switch activation.

Summary of Contents for LTF 225

Page 1: ...OPERATING INSTRUCTIONS LTF 85 225 325 425 535...

Page 2: ...ioning Start Procedure Caution Control Panel Main Functions Parameters Digital Input Connections Default Setting Values Cleaning And Maintenance of The Freezer Relocating or Moving The Freezer Disposi...

Page 3: ...personnel in the use of the freezer the temperature is 60 C There is a risk of frost bite if the contents or the sides of the inner container are touched In the event of breakdown or irregularities co...

Page 4: ...locked in the freezer whilst playing Electrical Connection The machine meets current EU directives Low voltage 2006 95 E E C Electromagnetic compatibility 2004 108 E E C The machine should be given e...

Page 5: ...he installation should be fused with a 16 A fuse Before Commissioning Clean the freezer both inside and out using a damp wrung out cloth Dry with a dry cloth The smell from the plastic parts in the fr...

Page 6: ...emperature display USE OF LEDS Each LED function is described in the following table 1 Press and release the key 2 The Lo message will be displayed followed by the minimum temperature recorded 3 By pr...

Page 7: ...DEFROST Push the DEF key for more than 2 seconds and a manual defrost will start HOW TO CHANGE A PARAMETER VALUE To change the parameter s value operate as follows 1 Enter the Programming mode by pre...

Page 8: ...sage will be displayed and the keyboard will be locked At this point it will be possible only to see the set point or the MAX o Min temperature stored 3 If a key is pressed more than 3s the POF messag...

Page 9: ...n Compressor ON time with faulty probe 0 255 min time during which the compressor is active in case of faulty thermostat probe With COn 0 compressor is always OFF COF Compressor OFF time with faulty p...

Page 10: ...r failure y the alarm relay is activated if a temperature alarm happens during a power failure n the alarm relay is never activated during a power failure ALF Alarm relay activation for all the alarms...

Page 11: ...1F parameter DOOR SWITCH INPUT i1F dor It signals the door status and the corresponding relay output status through the odc parameter no Fan normal any change CPr F_C Compressor OFF Since the door is...

Page 12: ...unction is enabled until the digital input is activated DIGITAL INPUTS POLARITY The digital input polarity depends on the i1P parameter i1P CL the input is activated by closing the contact i1P OP the...

Page 13: ...13 CONNECTIONS XR30CX 20A COMPRESSOR 12Vac dc supply connect to the terminals 7 and 8 24Vac dc supply connect to the terminals 7 and 8 120Vac supply connect to the terminals 7 and 8...

Page 14: ...n rE related to set Ab absolute rE Pr2 ALU Maximum temperature alarm Set 110 0 C Set 230 F 15 Pr1 ALL Minimum temperature alarm 50 0 C Set 58 F Set 50 0 Pr1 AFH Differential for temperature alarm reco...

Page 15: ...reful not to get damp water on the electrical parts or water into the vent holes as water and damp may damage the electrical parts and cause the freezer to short circuit 4 The ice formed on the inside...

Page 16: ...rting it If the freezer and its electrical parts are reconstructed the guarantee and safety regulations shall cease to apply If the freezer does not work call an authorised servicing engineer Contact...

Page 17: ...17 Wiring Diagram LTF 85 325 535...

Page 18: ...18 Wiring Diagram LTF 225...

Page 19: ...19 Wiring Diagram LTF 425...

Page 20: ...50 80 017 04 GB WWW ARCTIKO COM LAMMEFJORDSVEJ 5 DK 6715 ESBJERG N DENMARK TEL 45 70 20 03 28 FAX 45 70 20 03 29 INFO ARCTIKO COM WWW ARCTIKO COM...

Reviews: