Reset
Reset ratio
97/103 % of the pick-up current setting
Instant reset time and start-up reset
<80 ms (<50 ms in differential protection relays)
9.2.3.2 Voltage transformer supervision (60)
Table. 9.2.3.2 - 330. Technical data for the voltage transformer supervision function.
Measurement inputs
Voltage input
U
L1
, U
L2
, U
L3
U
L12
, U
L23
Voltage input magnitudes
RMS line-to-line or line-to-neutral voltages
Pickup
Pickup settings:
- Voltage (low pick-up)
- Voltage (high pick-up)
- Angle shift limit
0.05…0.50 × U
N
, setting step 0.01 × U
N
0.50…1.10 × U
N
, setting step 0.01 × U
N
2.00…90.00 deg, setting step 0.10 deg
Inaccuracy:
- Voltage
- U angle (U> 1 V)
±4.0 %U
SET
±3.0°
External line/bus side pickup (optional)
0
→
1
Time delay for alarm
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (U
M
/U
SET
ratio > 1.05/0.95)
±1.0 % or ±35 ms
Instant operation time (alarm):
- U
M
/U
SET
ratio > 1.05/0.95
<50 ms
VTS MCB trip bus/line (external input)
<50 ms
Reset
Reset ratio
97/103 % of the pick-up voltage setting
Reset time setting
Inaccuracy: Reset time
0.010…10.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
VTS MCB trip bus/line (external input)
<50 ms
No
Notte!
e!
• When turning on the auxiliary power of an IED, the normal condition of a stage has to be
fulfilled before tripping.
9.2.3.3 Circuit breaker wear monitoring
Table. 9.2.3.3 - 331. Technical data for the circuit breaker wear monitoring function.
Pick-up
Breaker characteristics settings:
- Nominal breaking current
- Maximum breaking current
- Operations with nominal current
- Operations with maximum breaking current
0.00…100.00 kA, setting step 0.001 kA
0.00…100.00 kA, setting step 0.001 kA
0…200 000 operations, setting step 1 operation
0…200 000 operations, setting step 1 operation
Pick-up setting for Alarm 1 and Alarm 2
0…200 000 operations, setting step 1 operation
A
AQ
Q-F213
-F213
Instruction manual
Version: 2.04
448