Figure. 7.1 - 232. AQ-F213 application example with function block diagram.
Protection functions
Control functions
Device I/O
AQ-F213
DI
1...6
DO
5+1
CT
3 (IL)
2 (I0)
Add-on
3 slots
Monitoring functions
THD
31st
CTS
CBW
Circuit
breaker
wear
DR
Disturbance
recorder
VTS
21FL
Fault
locator
Current-based
I>
50/51
(4)
I0>
50N/51N
(4)
CBFP
50/52BF
(1)
I0d>
(1)
87N
Ih>
(4)
50H/51H
/68H
(4)
I2>
46/46R
/46L
TF>
49F
(1)
U0>
59N
(4)
f>/<
81O
/81U
(8)
df/dt >/<
81R
(1)
Idir>
(4)
67
I0dir>
(4)
67N
P>
(1)
32O
P<
(1)
32U
Pr
(1)
32R
Voltage and current-based
VT
3 voltage
channels
0 → 1
79
OBJ
CLPU
Cold load
pick-up
SOTF
Switch-on-
to-fault
SGS
1...8
∆α
78
(1)
U1/U2>/<
47/27P
/59PN
(4)
Iarc>/I0arc>
50Arc>
/50NArc>
U>
59
(4)
U<
27
(4)
Voltage-based
OPTIONAL
7.2 Application example and its connections
This chapter presents an application example for the feeder protection IED.
Since two line-to-line voltages and the zero sequence voltage (U3) are connected, this application
uses the voltage measurement mode "2LL+U0" (see the image below). Additionally, the three phase
currents and the residual current (I01) are also connected. The digital inputs are connected to indicate
the breaker status, while the digital outputs are used for breaker control.
A
AQ
Q-F213
-F213
Instruction manual
Version: 2.04
392