Table. 5.3.10 - 102. Pick-up settings.
Name
Range
Step Default
Description
Pick-up
terms
0: 1 voltage
1: 2 voltages
2: 3 voltages
-
0: 1
voltage
Selects the pick-up criterion.
U
set
50.00…150.00
%U
n
0.01
%U
n
105 %U
n
The pick-up setting.
Delay type 0: DT
1: IDMT
-
0: DT
Selects the delay type time counter. The selection possibilities are
dependent (IDMT, Inverse Definite Minimum Time) and independent (DT,
Definite Time) characteristics.
Time dial
setting k
0.01...60.00
0.01
0.01
The time dial/multiplier setting for IDMT characteristics. This setting is
only visible when "IDMT" is the selected delay type.
Definite
operating
time delay
0.000...1800.000
s
0.005
s
0.04 s
The definite time operating delay. This setting is active and visible when
"DT" is the selected delay type.
When set to 0.000 s, the stage operates as instant without added delay.
When the parameter is set to 0.005...1800 s, the stage operates as
independent delayed.
IDMT
multiplier
0.01...25.00
0.01
1.00
The IDMT time multiplier in the U
m
/U
set
power. This setting is only visible
when "IDMT" is the selected delay type.
Release
time delay
0.000...150.000
s
0.005
s
0.06 s
Determines the time allowed between pick-ups if the pick-up has not led
into a trip operation. During this time the START signal is held on for the
timers if the delayed pick-up release is active.
Delayed
pick-up
release
0: Yes
1: No
-
0: Yes
Selects the resetting characteristics. Either time-delayed or instant after
the pick-up element is released. If activated the START signal is reset
after a set release time delay.
Op.Time
calc reset
after
release
time
0: Yes
1: No
-
0: Yes
Selects the operating timer resetting characteristics. When actived, the
operating time counter is reset after a set release time if the pick-up
element is not activated during this time. When disabled, the operating
time counter is reset directly after the pick-up element reset.
Continue
time
calculation
during
release
time
0: Yes
1: No
-
1: No
Selects the time calculation characteristics. If activated, the operating
time counter continues until a set release time even if the pick-up
element is reset.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.10 - 103. Information displayed by the function.
Name
Range
Step
Description
U< pick-
up setting
0.0...1 000 000.0 V
0.1 V
The primary voltage required for tripping. The displayed pick-up voltage
level depends on the pick-up setting and the voltage transformer
settings.
Expected
operating
time
0.000...1800.000 s
0.005 s
Displays the expected operating time when a fault occurs. When IDMT
mode is used, the expected operating time depends on the measured
voltage value. If the measured voltage changes during a fault, the
expected operating time changes accordingly.
A
AQ
Q-F213
-F213
Instruction manual
Version: 2.04
165