Level Menu
Insert (Fig. 79)
In this window it is possible to modify the state of the plugs de
-
pending on the levels read by the sensor (LEV 1 or LEV 2).
To set this program, proceed as follows:
Main screen
Main Menu
Level
Programs
Insert.
•
Select the state of the sensor (OFF, LEV 1, LEV 2) by using
the keys
.
•
Set the minimum time (in seconds) of program activation
independently from the sensor status.
•
Set the maximum time (in seconds) which the output,
selected afterwards, must remain active; use the keys
to modify the value.
•
Select with keys
the output which is to be utilized while
using the keys
to modify its state; it is possible to choose
when to activate (output highlighted with symbol above) or
deactivate (only with the symbol above) the outputs in corre
-
spondence to the state of the level sensor selected above.
When completed press “Enter”
to memorize the program.
Show/Modify/Delete
See page 31.
Delete All
See page 31.
The example indicated in figure (Fig. 80) shows the activation
of the automatic topoff pump on plug “C”: whenever the level
sensor moves to the position LEV 1, output “C” is activated
(which activates the automatic topoff pump).
If the level sensor’s state does not change (returns to position
LEV 2) inside the set time (Max Time) the program is blocked
and the control unit displays an error message.
On the main screen the symbol
will appear, accompanied
by an acoustic signal; which indicates an anomaly in the
automatic topoff system, such as a damaged level sensor or
pump, or perhaps the absence of water in the “hopper”.
In the event of an anomaly, the following message will appear
(Fig. 81) which will consequently block the program.
(Fig. 79)
Programs
OFF
Minimum time
0s
Max Time: OFF
PU01 A B C D E F
(Fig. 80)
Programs
LEV 1
Minimum time
5s
Max Time: 10s
Automatic topoff pump
PU01 A B
C
D E F
(Fig. 81)
Sensor program
error:
Level