background image

Cleaning the units 

The unit housing must be opened 
to allow the inside of the unit 
to be cleaned and to provide

 

access to electrical components

1

Remove the mains plug from

    the mains socket

 

 

NOTE

Installation work may only 
be carried out by authorised 
qualified technicians

.

by authorised specialists

.

 

Air dehumidifIers

14

2

Clean the condenser fins 

    by blowing

with suction 

    or using a smooth brush

 

3

Exercise

 

extreme

 

caution

 

when

 

    

cleaning the condenser

The

 

fine

 

    

aluminium fins bend very easily

.

 

4

Never subject to sharp jets 

    of water 

(

high

-

pressure

 

cleaners

).

 

5

Clean the evaporator fins

for 

    example with a lukewarm soap 
    solution 

(

or similar

).

 

6

Rinse with clean water 

    to remove

 

any

 

remaining

 

soap

.

 

7

Clean the internal surfaces 

    of the entire

 

unit

 

as

 

well

 

    

as the fan blade

.

 

8

Once cleaning has been 

    completed

the unit should 

    be dried with care

    

Take

 

particular

 

care

 

with

 

    

electrical components

!

 

 

9

Re

-

install all dismantled 

    components in reverse

 

order

 

10

Carry out a unit function check 

    and electrical safety check

 

ATTENTION

An electrical safety check must 
be carried out in accordance 
with VDE 0701 after any work 
on the units

.

!

Troubleshooting

The units are

 

manufactured

 

using state

-

of

-

the

-

art production

 

methods and tested several times 
to verify their correct

 

function

However

if

 

a

 

functional

 

fault

 

should occur

the

 

unit

 

should

 

first

 

be checked in accordance

 

with

 

the following list

:

The unit does not start

■   

Check the setting 
of the operating switch

The green

 

control

 

lamp

 

should

 

illuminate

■   

Check

 

mains

 

connection

 

220V

/

1

~/

50

 

Hz

■   

Check mains plug and cable for 
damage

■   

Check the customer

-

provided

 

mains protection

Minimum protection

 

10A

 

■   

Check the level and correct

 

positioning of the condensate 
container

The front

 

sealing

 

flap

 

must

 

be fully closed and locked

 

■  

 

Check the function 
of the micro switch

■   

Check the setting 
of the humidity switch 

(

accessories

). 

The pre

-

set

 

value

 

must

 

be

 

lower than the relative

 

humidity

 

in the room

.

 

■   

Check the humidity switch 
adapter for damage and correct

 

positioning

The unit runs but does not 
form any condensate

■   

Check the room

 

temperature

.

The operating range of the unit 
is between 3

°

C and 32

°

■   

Check the humidity of the air

min

40

RH required

■   

Check the

 

setting

 

of the humidity 

switch

set a lower humidity 

value if necessary

■   

Check the dust filter 
for contamination

 

and clean 

or replace

 

if

 

necessary

■   

Check the evaporator 
and condenser fins for 
contamination and clean 
if necessary

■   

Check the evaporator for ice 
or rime formation If ice has 
formed

check the functionality 

of the automatic defrost

 

and the temperature

 

sensor

 

■   

Check whether or not 
the evaporator temperature

 

is below room

 

temperature

 

If this is not the case

check 

the automatic defrost

 

or

 

room

 

temperature

The unit does not start

  

Check whether or not 
the condensate container 
is inserted correctly

 

and

 

that

 

the front

 

sealing

 

flap

 

is

 

locked

  

Check whether or not mains 
power is available

NOTE

If the unit fails to function 
correctly after the checks have 
been carried out

an authorised 

specialist must be informed

.

ATTENTION

Work

 

on

 

the

 

refrigerant

 

system and on the electrical 
equipment must only 
be conducted by a specially

-

authorised specialist

!

Summary of Contents for DH-15

Page 1: ... INSTALLATION AND INSTRUCTION MANUAL www aqua it DHseries Technology Operation Replacement parts Airdehumidifers AQUA Read these operating instructions carefully before commissioning using this device DH 15 DH 6 DH 4 DH 2 ...

Page 2: ......

Page 3: ...liabilityaccepted forerrors ormisprints Airdehumidification 4 Safetynotes 6 Intended use 7 Customerservice andwarranty 7 Environmental protection and recycling 7 Unitdescription 8 Set up 9 Commissioning 10 Decommissioning 12 Transportation 12 Care and maintenance 13 Troubleshooting 14 Electrical connection diagram 15 Maintenance protocol 16 Technical data 17 3 Air dehumidifIers ...

Page 4: ...released from parts of a building ormaterials is absorbed bythe surrounding air As a result the moisture content increases which ultimatelygives rise to corrosion mould rot peeling ofpaintand otherunwanted damage Bywayofexample the diagram shows the corrosion rate of metal in different levels of humidity Air dehumidification With regard to energy consumption airdehumidification has one distinctadv...

Page 5: ... iteasierfor the temperature to fall below it Building materials and structures are capable of absorbing considerablevolumes ofwater such as brick90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The drying ofmoistmaterials such as masonryis effected as follows The moisture moves from the inside ofthe material to its surface Evaporation occurs on the surface Transfer ofwatervapourto ...

Page 6: ...d to a greater extent by the speed at which the material or building section loses its moisture Safety notes The unitswere subjected to exten sive material functional and qual ityinspections priorto delivery However dangers can emanate from the units if they are used improperly or not as intended by untrained personnel The following notes mustbe observed in full The units maynotbe installed oroper...

Page 7: ...terials are environmentally friendly and can be recycled Byrecycling packaging materials you make avaluable contribution to the reduction of waste and conservation ofrawmaterials Therefore only dispose of packaging material at appropriate collection points Disposal of the old unit The manufacturing process for the units is subjectto continuous qualitycontrol Onlyhigh grade materials are processed ...

Page 8: ...he cooled and dehumidified air is re heated by the condenser heatexchanger and blown back into the room through the outlet grille The processed dry heated airthen re mixes with the room air Continuous circulation of the room airthrough the unit gradually reduces the relative humidity RH in the room to the desired humiditylevel Depending on the room temperature and the humidity only30 40 electrical...

Page 9: ...s ofheat Aircirculation is improved ifthe unitis setup approx 1 m above the ground The room being dried ordehumidified mustbe closed to the neighbouring atmosphere Avoid having opened windows and doors etc and avoid frequent entry to or exit from the room as much as possible Ifthe units are to be used in dustyenvironments orstables appropriate care and maintenance measures should be taken accordin...

Page 10: ... orfilter mustbe cleaned orreplaced immediately NOTE In room temperatures below 10 C and relative humidity below40 economical use ofthe unitcan no longer be guaranteed NOTE The units are only functionalwhen operatedwith a correctlyinserted condensate container Air dehumidifIers Turn ON orOFF Enterparametersetting status Check or set the parameter Invalid Set timer Targethumidityvalue Measuredvalue...

Page 11: ...C2 C3 C4 C5 C6 C7 Heating function Condensation coil temperature Humidity sensor detects deviation Press after opening delay detection time Enter the defrost point temperature Exit defrost point temperature Maximum defrost time Parameter Description Default values Code Meaning Para meter No 0 1 1 20 99 5 5 0 20 90min 40 10 10 1 0 15 8 2 12min 8 Press the 3 seconds to enterthe parameterquerysetmenu...

Page 12: ...densate into a lower lying drain To operate the units the condensate containermust always be inserted correctly and the sealing flap mustalways be locked NOTE Ensure thatthe drainage hose is placed atan angle to the drain to allow the condensate to drain from the condensate container withouthindrance The following procedure must be followedwhen connecting awaterhose 1 Open the frontsealing flap an...

Page 13: ...re and maintenance All moving parts have a low maintenance permanentcoat oflubricant The refrigerant system is designed as a hermeticallysealed system and mayonlybe repaired bya specialist NOTE Regularcare and maintenance is fundamental to a long service life and fault free operation ofthe unit ATTENTION Before undertaking any workon the units the mains plug mustbe removed from the mains socket Ke...

Page 14: ...control lamp should illuminate Check mains connection 220V 1 50 Hz Checkmains plug and cable for damage Checkthe customer provided mains protection Minimum protection 10A Checkthe level and correct positioning ofthe condensate container The front sealing flap must be fullyclosed and locked Checkthe function ofthe micro switch Checkthe setting ofthe humidityswitch accessories The pre set value must...

Page 15: ...5 FM CM Y G WIRE CONTROLLER HIGH PRESSURE LOW PRESSURE TRANSFORMER U V W AMBIENT TEMPERATURE COIL TEMPERATURE OBLIGATE OBLIGATE YW BK RD HUMIDITY TEMP FM L K1 N A B C phase relay 380V 3 Phase 50Hz OUT 1 COMP CN19 LED 4 WAY FM H AC N CN1 CN2 SW1 220V AC 12V AC OUT3 OUT4 OUT5 FM CM Y G WIRE CONTROLLER HIGH PRESSURE LOW PRESSURE TRANSFORMER N L R S C AMBIENT TEMPERATURE COIL TEMPERATURE OBLIGATE OBLI...

Page 16: ... Date Signature 19 Date Signature 20 Date Signature Comments Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unitcleaned outside Unitcleaned inside Fan blade cleaned Fan housing cleaned Condensercleaned Vaporiser cleaned Fan function checked Air inlet grid with flter cleaned Unitchecked fordamage Safetydevices checked All fastening screws checked Electrical safetycheck Tes...

Page 17: ...kg DH 15 3 32 40 100 15 2 15 0 4500 Φ20 Scroll R22 2400 380V 3 50 8 1 2 3 6 2 40 Hotgas 53 770 770 995 1090 165 1 Noise level measurement DIN 45635 13 KL 3 2 Dimensions in withouttransportation bracket We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process Technical data Air dehumidifIers 17 DH 6 3 32 40 100 6 2 6 0 2800 Φ20 Rot...

Page 18: ......

Reviews: