TROUBLE SHOOTING 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

Unit shuts down 
automatically 

during startup 
process. 

LCD/LEDs and buzzer 
will be active for 3 

seconds and then 
complete off. 

The battery voltage is too low 

(<1.91V/Cell) 

1. Re-charge battery. 

2. Replace battery. 

No response after 
power on. 

No indication. 

1. The battery voltage is far too 

low. (<1.4V/Cell) 
2. Battery polarity is connected 

reversed. 

1. Check if batteries and the 

wiring are connected well. 
2. Re-charge battery. 

3. Replace battery. 

Mains exist but the 
unit works in 

battery mode. 

Input voltage is 
displayed as 0 on the 

LCD and green LED 
is flashing. 

Input protector is tripped 

Check if AC breaker is tripped 
and AC wiring is connected 
well. 

Green LED is 
flashing. 

Insufficient quality of AC power. 
(Shore or Generator) 

1. Check if AC wires are too 

thin and/or too long. 
2. Check if generator (if 
applied) is working well or if 
input voltage range setting is 

correct. (UPS

Appliance) 

Green LED is 

flashing. 

Set “Solar First” as the priority of 

output source. 

Change output source 

priority to Utility first. 

When the unit is 
turned on, internal 

relay is switched on 
and off repeatedly. 

LCD display and 

LEDs are flashing 

Battery is disconnected. 

Check if battery wires are 

connected well.   

Buzzer beeps 
continuously and 

red LED is on. 

Fault code 07 

Overload error. The inverter is 

overload 110% and time is up. 

Reduce the connected load 

by switching off some 
equipment. 

Fault code 05 

Output short circuited. 

Check if wiring is connected 
well and remove abnormal 
load.   

Temperature of internal converter 
component is over 120°C.   

Check whether the air flow of 
the unit is blocked or 
whether the ambient 

temperature is too high. 

Fault code 02 

Internal temperature of inverter 

component is over 100°C. 

Fault code 03 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 

batteries are meet 
requirements. 

Fault code 01 

Fan fault 

Replace the fan. 

Fault code 06/58 

Output abnormal (Inverter 
voltage below than 190Vac or is 
higher than 260Vac) 

1. Reduce the connected 
load. 
2. Return to repair center 

Fault code 
08/09/53/57 

Internal components failed. 

Return to repair center. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error 

happens again, please return 
to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced. 

Fault code 56 

Battery is not connected well or 
fuse is burnt. 

If the battery is connected 
well, please return to repair 

center. 

 

 

 

Summary of Contents for VEYRON IV 3.2KW

Page 1: ...VEYRON IV 3 2KW SOLAR INVERTER CHARGER Version 1 0 User Manual...

Page 2: ...12 Power ON OFF 12 Operation and Display Panel 12 LCD Display Icons 13 LCD Setting 16 LCD Display 30 Operating Mode Description 36 Faults Reference Code 41 Warning Indicator 42 CLEARANCE AND MAINTENAN...

Page 3: ...rectly operate this inverter charger 8 Be very cautious when working with metal tools on or around batteries A potential risk exists to drop a tool to spark or short circuit batteries or other electri...

Page 4: ...control panel Configurable AC PV output usage timer and prioritization Configurable AC Solar charger priority via LCD control panel Configurable battery charging current based on applications via LCD...

Page 5: ...ection for the details 3 Touchable function keys 4 PV connectors 5 AC input connectors 6 AC output connectors Load connection 7 Battery connectors 8 Circuit breaker 9 Dry contact 10 USB port as USB co...

Page 6: ...Unit Consider the following points before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order...

Page 7: ...battery connection To reduce risk of injury please use the proper recommended cable and terminal size as below Recommended battery cable and terminal size Model Typical Amperage Battery capacity Wire...

Page 8: ...output connectors WARNING All wiring must be performed by a qualified personnel WARNING It s very important for system safety and efficient operation to use appropriate cable for AC input connection T...

Page 9: ...es such as air conditioner requires at least 2 3 minutes to restart because it s required to have enough time to balance refrigerant gas inside of circuits If a power shortage occurs and recovers in a...

Page 10: ...the proper cable size as recommended below Model Wire Size Cable mm2 Torque value 3 2KW 12AWG 4 1 0 1 2Nm Recommended Panel Configuration When selecting proper PV modules please be sure to consider t...

Page 11: ...W 9pcs in series 9pcs 4995W 10pcs in series 10pcs 5550W Solar Panel Spec reference SOLAR INPUT Q ty of panels Total Input Power 150V Start up Voltage Voc Number of modules in series 500V Max PV Array...

Page 12: ...undled CD WiFi Connection This unit is equipped with a Wi Fi transmitter Wi Fi transmitter can enable wireless communication between off grid inverters and monitoring platform Users can access and con...

Page 13: ...utility first or SUB solar first Battery voltage Low DC warning voltage Open Close Battery voltage Setting value in Program 13 or battery charging reaches floating stage Close Open Program 01 is set...

Page 14: ...ply press On Off switch located on the side of the inverter to turn on the unit Operation and Display Panel The operation and the LCD module shown in the chart below includes six indicators six functi...

Page 15: ...y Constant Current mode Constant Voltage mode 2V cell 4 bars will flash in turns 2 2 083V cell The right bar will be on and the other three bars will flash in turns 2 083 2 167V cell The right two bar...

Page 16: ...am 16 Charger source priority is selected as Solar only Output source priority setting display Indicates setting program 01 Output source priority is selected as Utility first Indicates setting progra...

Page 17: ...ts to the mains Indicates unit connects to the PV panel Indicates battery type Indicates parallel operation is working Indicates unit alarm is disabled Indicates Wi Fi transmission is working Indicate...

Page 18: ...energy provides power to the loads as first priority If solar energy is not sufficient to power all connected loads Utility energy will supply power to the loads at the same time SBU priority Solar e...

Page 19: ...er Defined If User Defined is selected battery charge voltage and low DC cut off voltage can be set up in program 26 27 and 29 Pylontech battery If selected programs of 02 26 27 and 29 will be automat...

Page 20: ...02 26 27 and 29 will be automatically set up No need for further setting Please contact the battery supplier for installation procedure ISC If selected setting value in program 26 is 28V program 27 is...

Page 21: ...V Increment of each click is 1V 13 Setting voltage point back to battery mode when selecting SBU SBU priority in program 01 Setting range is FUL and from 24V to 31V Increment of each click is 1V Batte...

Page 22: ...eturn to default display screen default If selected no matter how users switch display screen it will automatically return to default display screen Input voltage output voltage after no button is pre...

Page 23: ...rement of each click is 0 1V 29 Low DC cut off voltage If battery power is only power source available inverter will shut down If PV energy and battery power are available inverter will charge battery...

Page 24: ...t Setting range is from 0 to 90 days Increment of each click is 1 day 36 Equalization activated immediately Enable Disable default If equalization function is enabled in program 30 this program can be...

Page 25: ...Not reset Default Reset 84 Data log recorded interval The maximum data log number is 1440 If it s over 1440 it will re write the first log 3 minutes 5 minutes 10 minutes default 20 minutes 30 minutes...

Page 26: ...nge is from 1 to 12 89 Time setting Year For year setting the range is from 17 to 99 91 On Off control for RGB LED It s necessary to enable this setting to activate RGB LED lighting function Enabled d...

Page 27: ...Power cycling Power wheel Power chasing Solid on Default 95 Data Presentation of data color Solar input power in watt Battery capacity percentage Default Load percentage 96 Background color of RGB LE...

Page 28: ...26 Blue Sky blue Default Purple Other 97 Data Color for RGB LED Pink Orange Yellow Green Blue Sky blue Purple Default Others...

Page 29: ...CD Screen Step 3 Press or button to enter the selectable setting programs detail descriptions in Step 4 Step 4 Please select setting program by following the procedure Program Operation Procedure LCD...

Page 30: ...st Timer Press button to select staring time Press or button to adjust values and press to confirm Press button to select end time Press or button to adjust values press button to confirm The setting...

Page 31: ...button to adjust values press button to confirm The setting values are from 00 to 23 with 1 hour increment Press button to set up Solar Utility Timer Press button to select staring time Press or butto...

Page 32: ...order Selectable information LCD display Default Display Screen Utility voltage Utility frequency Utility current switch every 5 second Input Voltage 230V Input frequency 50Hz Input Voltage 230V Inpu...

Page 33: ...ltage 50 4V Bulk charging voltage 56 4V Charging current 20A Battery voltage 53 9V Floating charging voltage 54 0V Charging current 1A Battery voltage 50 4V Low DC cut off voltage 44 0V Discharging cu...

Page 34: ...reen Output voltage load in VA load in Watt switch every 5 second Output frequency Load in VA 2 4kVA Output frequency 50Hz Load in Watt 2 4kW Output frequency 50Hz Real date Real date Dec 14 2020 Real...

Page 35: ...33 PV energy generated today PV energy generated today 888Wh PV energy generated this month PV energy generated this month 8 88kWh PV energy generated this year PV energy generated this year 88 8kWh...

Page 36: ...erated totally Total PV energy generated 888kWh Load output energy today Load energy Today 888Wh Load output energy this month Load energy this month 8 88kWh Load output energy this year Load energy t...

Page 37: ...oad output energy Total Load Output energy 888kWh Main CPU version checking Main CPU version 00050 72 Secondary CPU version checking Secondary CPU version 00022 01 Wi Fi version checking Wi Fi version...

Page 38: ...turned on yet but at this time the inverter can charge battery without AC output No output is supplied by the unit but it still can charge batteries Charging by utility and PV energy Charging by utili...

Page 39: ...mode Note Fault mode Errors are caused by inside circuit error or external reasons such as over temperature output short circuited and so on PV energy and utility can charge batteries Charging by uti...

Page 40: ...ty If SUB solar first is selected as output source priority and solar energy is not sufficient to provide the load solar energy and the utility will provide the loads and charge the battery at the sam...

Page 41: ...ains It will also charge the battery at line mode Power from utility Power is only generated from PV energy and feeds PV energy to grid when battery is not connected PV energy charges battery provides...

Page 42: ...ovide output power from battery and or PV power Power from battery and PV energy PV energy will supply power to the loads and charge battery at the same time No utility is available Power from battery...

Page 43: ...Output short circuited 06 Output voltage is too high 07 Overload time out 08 Bus voltage is too high 09 Bus soft start failed 10 PV over current 11 PV over voltage 12 DCDC over current 13 Battery dis...

Page 44: ...Battery is over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds 15 PV energy is low Beep...

Page 45: ...keeps dusk from your inverter and increases product reliability in harsh environment Clearance and Maintenance Step 1 Please remove the screw on the two sides of the inverter Step 2 Then dustproof ca...

Page 46: ...float stage when the setting equalization interval battery equalization cycle is arrived or equalization is active immediately the controller will start to enter Equalize stage Equalize charging time...

Page 47: ...ax AC Input Current 60A Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High Loss Return Frequency 63 1Hz Output...

Page 48: ...0s 105 130 load Surge Capacity 2 rated power for 5 seconds Low DC Warning Voltage 23 0Vdc 22 0Vdc load 50 load 50 Low DC Warning Return Voltage 23 5Vdc 23 0Vdc load 50 load 50 Low DC Cut off Voltage 2...

Page 49: ...harging Algorithm 3 Step Charging Curve Time Battery Voltage per cell Charging Current 100 50 Bulk Constant Current Absorption Constant Voltage Maintenance Floating Current Voltage minimum 10mins maxi...

Page 50: ...cifications MODEL 3 2KW Safety Certification CE Operating Temperature Range 10 C to 50 C Storage temperature 15 C 60 C Humidity 5 to 95 Relative Humidity Non condensing Dimension D W H mm 115 x 300 x...

Page 51: ...dly LCD display and LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is overloa...

Page 52: ...al ID to each battery module for normal operation We can set up the ID code for each battery module by rotating the PIN number on the ID switch From number 0 to 9 the number can be random no particula...

Page 53: ...It s required to set up master battery on the third group with this setting and slave batteries are unrestricted 0 0 1 Multiple group condition It s required to set up master battery on the fourth gro...

Page 54: ...uld be USE Step 2 Press manual ON OFF button for 5 secs in the front panel the battery will start up Step 3 Press more than three seconds to start Lithium battery power output ready Step 4 Turn on the...

Page 55: ...cable to connect any inverter no need to connect to a specific inverter and Lithium battery Simply set this inverter battery type to PYL in LCD program 5 Others should be USE Step 2 Switch on Lithium...

Page 56: ...tallation 2 Use one custom made RJ45 cable to connect any inverter no need to connect to a specific inverter and Lithium battery Simply set battery type of this inverter to WEC in LCD program 5 The re...

Page 57: ...verter and Lithium battery Simply set battery type of this inverter to SOL in LCD program 5 The remaining inverters are set as USE Step 2 Open DC isolator and switch on Lithium battery Step 3 Turn on...

Page 58: ...ation between the inverter and battery is successful it will show code 60 to stop charging and discharging battery Communication lost only available when the battery type is not setting as AGM Flooded...

Page 59: ...ccurs Allows users to query inverter history data 2 WatchPower App 2 1 Download and install APP Please scan the following QR code with your smart phone and download WatchPower App Android system iOS s...

Page 60: ...Wi Fi Config page There are detailed setup procedure listed in How to connect section and you may follow it to connect Wi Fi Enter the Settings Wi Fi and select connected Wi Fi name The connected Wi F...

Page 61: ...Fi module and the Internet If the connection fails please repeat Step 2 and 3 Diagnose Function If the module is not monitoring properly please tap on the top right corner of the screen for further de...

Page 62: ...ed name and password to login Note Tick Remember Me for your login convenience afterwards Overview After login is successfully you can access Overview page to have overview of your monitoring devices...

Page 63: ...r to add device This part number label is pasted on the bottom of remote LCD panel After entering part number tap Confirm to add this device in the Device list For more information about Device List p...

Page 64: ...en there is a dynamic power flow chart to show live operation It contains five icons to present PV power inverter load utility and battery Based on your inverter model status there will be Standby Mod...

Page 65: ...nfirm to complete name modification Device Information Data Users can check up Basic Information Product Information Rated information History and Wi Fi Module Information by swiping left Basic Inform...

Page 66: ...ctly in the column Each function setting is saved by clicking Set button Please refer to below parameter setting list for an overall description and be noted that the available parameters may vary dep...

Page 67: ...e Disable Functions LCD Auto return to Main screen If enable LCD screen will return to its main screen after one minute automatically Fault Code Record If enabled fault code will be recorded in the in...

Reviews: