19
240V
11
Maximum utility charging
current
Note: If setting value in
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02 for
utility charger.
30A (default)
Setting range is from 2A, then
10A to 100A. Increment of
each click is 10A.
12
Setting voltage point back
to utility source when
selecting
“SBU”
(SBU
priority) in program 01.
23V (default)
Setting range is from 22V to
25.5V. Increment of each click
is 1V.
13
Setting voltage point back
to battery mode when
selecting
“SBU”
(SBU
priority) in program 01.
Setting range is FUL, and from 24V to 31V. Increment of each
click is 1V.
Battery fully charged
27V (default)
16
Charger source priority:
To configure charger source
priority
If this inverter/charger is working in Line, Standby or Fault
mode, charger source can be programmed as below:
Solar first
Solar energy will charge
battery as first priority.
Utility will charge battery only
when solar energy is not
available.
Solar and Utility (default)
Solar energy and utility will
charge battery at the same
time.